Updated: 29JAN2010

PORTABLE ELECTRICAL SUBMERSIBLE PUMP

FOR USS

DATE:

Ref:(a) MIP 6641/006 Damage Control Stations; PMS MRC A-11 Inspect and Test Electric Submersible Pump

(b) MIP 3000/001 Misc. Shipboard Electrical Equipment and Installed Receptacles, PMS MRC A-3R Inspect Electrical Submersible Pump; Measure Circuit Resistance to

Ground (MUST BE CONDUCTED WITHIN 30 DAYS PRIOR TO ACCOMPLISHING MIP 6641/006 MRC A-11)

(c) NAVSHIPS Technical Manual 0347-183-0000, A.C. Portable Submersible Pump Model 777H (Aluminum) and Model 777D (Bronze)

(d) AEL 2-880044240 & 2-880044270

(e) Naval Ships Technical Manual S9086-KC-STM-010/Ch-300R-6, Electric Plant - General

Ref(s) / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT / SAT/ UNSAT
SERIAL NUMBERS
A. Static Equipment and Electrical Cable Inspection:
1. Are the pump cap threads clean, lubricated and in good condition? / Ref (a)
2. Is the tending line properly secured to the pump and cable? Note: Tending line will be nylon double braided or plaited 2” 50’. Should be secured to the pump so that the line takes the weight of the pump and not the electrical cord. Line should be seized to the electrical cable along the length of the cable. / Refs (a) and (c)
NAVSEA TIP (Attachment ESP-001)
3. Is the power cable free of deterioration, kinks or visible defects and electrically safety check IAW PMS? / Refs (a) and (b)
4. Is the cable stuffing tube properly packed and watertight? / Refs (a) and (b)
5. Is the switchbox cover gasket in good condition? / Ref (a)
6. Is the switchbox interior free of water and moisture with spare silver-tipped fuses in place? / Refs (a) and (b)
7. Is the star strainer clean? / Ref (a)
8. Does the foot valve operate freely? / Ref (a)
9. Are two, 2 1/2-inch hard rubber suction hoses available IAW AEL for each pump and inspected for damage and deterioration with gaskets in place? / Ref (d)
10. Inspect fuse continuity, verify proper amperage and voltage rating.
Note: IAW NSTM 300; silver-plated fuses are the only fuses authorized onboard naval ships. ESP fuse rating should be 500V, 15AS, BUSS F16. / Ref (e) Para 300-2.5.4.1
11. Measure resistance between dummy receptacle and each exposed metal part of the pump with multimeter. Resistance must be less than 1 ohm. / Ref (b)
12. With the power unplugged and the power switch in the “ON” position, measure insulation resistance (dummy plug removed) between the pump casing and each power lead plug contact with meggar. Minimum resistance is 1 megohm. / Ref (b)
13. With the power unplugged and the power switch in the “OFF” position, measure insulation resistance (dummy plug removed) between the pump casing and each power lead plug contact with meggar. Minimum resistance is 1 megohm. / Ref (b)
B. Operational Test:
1. Does the pump operate and rotate in the proper direction? / Refs (a) and (c)
2. Is the pump free of rubbing, binding or other unusual noises during the operational test? / Refs (a) and (c)
3. Does the 440V outlet have the correct phase rotation? / Ref (d)
Comments/Discrepancies

Assessor(s):Date:

1