Sunoco Logistics L.P. and Affiliates

CONSTRUCTION
STANDARDS / PAINTING OF TANKS, PIPES, EQUIPMENT, & STEEL STRUCTURES /
ENGR-PR-1100
Issuing Dept: Engineering
/ Document Authorizer:
Manager Engineering Specialists & Standards
Revision No.: 03
/ Revision Date: 01/22/2013 / Document Reviewer:
Sunoco Logistics SME
Next Review Date: 3/26/2015
/ Document Author:
Team Lead of Engineering Standards Committee
Document Administrator:
Engineering Standards Document Control Coordinator
Sunoco Logistics L.P. & Affiliates
PAINTING OF TANKS, PIPES, EQUIPMENT, & STEEL STRUCTURES
  • Engineering Dept.

Lindy Barile

Table of Contents

1.0 SCOPE OF SPECIFICATION 3

2.0 GENERAL REQUIREMENTS 4

3.0 PRODUCTS 5

CHART 1: New Steel (Shop Applied Primer and Intermediate Coats; Field Applied Finish Coat) 5

Notes (Chart 1): 6

CHART 2: New or Existing Steel (Field Applied Primer, Intermediate and Finish Coats) 7

Notes (Chart 2): 8

CHART 3: Existing Steel (High Pressure Water Wash Surface Preparation) 9

Notes (Chart 3): 10

4.0 INSPECTION 11

5.0 LABELING, DECALS, AND STENCILS 11

SURFACE PREPARATION STANDARDS 12

SURFACE PREPARATION STANDARDS - WATER JETTING STANDARDS 15

CHART 4: Pressure Categorization 15

CHART 5: Visual Conditions of Surface Cleanliness 16

CHART 6: Non-Visual Conditions Of Surface Cleanliness 17

REVISION LOG 17

1.0 SCOPE OF SPECIFICATION

1.1  Unless stated otherwise on the construction drawings or in the project scope of work description, this specification covers the requirements for field painting exterior surfaces of aboveground tanks, piping, equipment and structural steel.

1.2  This specification includes both new construction and repainting requirements. The painting of buildings (interior and exterior) is not covered in this specification.

1.3  Tank internal linings are not covered in this Specification.

2.0 GENERAL REQUIREMENTS

2.1  The Contractor shall provide all necessary labor, material and equipment, as required to complete all work as specified.

2.2 The manufacturer's product data sheets for specified paint materials are incorporated as requirements by reference. The Contractor shall perform all work in strict compliance with these data sheets. Contractor shall arrange for a pre-job meeting with the selected coatings manufacturer area representative prior to job start up to review project scope of work, and coatings manufacturer installation requirements.

2.2  The Painting Contractor shall complete a copy of the attached Sunoco Logistics Coating Inspection Report each day. The Contractor shall retain one copy of this sheet, and one sheet shall be given to the Owner's Representative.

2.3  The following materials and surfaces are not to be coated unless specified otherwise on the construction drawings or in the scope of work description:

1.  Equipment name plates, tags, labels, or other identification.

2.  Concrete, glass, fiberglass, brick or glazed tile.

3.  Stainless steel, brass, bronze, copper or other non-ferrous surfaces.

4.  Insulation jacketing.

5.  Plastic pipe or electrical conduit.

6.  Galvanized surfaces.

7.  Interior surfaces of equipment, valve stems or moving parts.

8.  Electrical devices, instruments or similar equipment.

3.0 PRODUCTS

3.1  All paint materials shall be manufactured by The Sherwin-Williams Company (SW), International Paint LLC/Akzo Nobel (IP), or Carboline (C).

3.2  The following charts summarize several surface preparation and coating systems that are to be used, depending on field conditions.

CHART 1: New Steel (Shop Applied Primer and Intermediate Coats; Field Applied Finish Coat)

SURFACE PREPARATION: All surfaces to be coated shall be free from grease and oil; solvent cleaning as per SSPC-SP1 may be required. All surfaces to be coated shall be abrasive blasted to SSPC-SP10 Near-White Blast Standard with a minimum sharp angular profile of 2.0-3.0 mils. All mill scale must be completely removed. Prepared surfaces must be primed within eight hours of blasting or before flash rusting occurs. All published environmental conditions and recoat windows must be followed.
Coat / Product Name / Volume Solids / Recommended Min / DFT Range Max / Coverage (sq.ft./gal) Theoretical No Loss
1st / (Shop Applied Primer)
(SW) Macropoxy 646 Fast Cure Epoxy
(C) Carboguard 60 Epoxy
(IP) Intergard 345 Epoxy / 72%
72%
70% / 4.0
4.0
4.0 / 6.0
6.0
6.0 / 192-288
192 – 288
187-280
2nd / (Shop Applied Intermediate)
(SW) Recoatable Epoxy Primer
(C) Carboguard 60 Epoxy
(IP) Intergard 345 Epoxy / 65%
72%
70% / 4.0
4.0
4.0 / 6.0
6.0
6.0 / 176-260
192 – 288
187-280
3rd / (Field Applied Finish)
(SW) Epolon 7 HS Porcelain White
(C) Carboguard 893SG Tank White
(IP) Intergard 1033 Tank White Epoxy
(See notes below) / 63%
63%
62% / 2.0
2.0
2.0 / 4.0
4.0
4.0 / 265-400
265 – 400
249-498

Notes (Chart 1):

1.  All plate ends and areas where welding is to be done shall be blasted as specified above but receive a 2” stand-back during the shop applied coating application only.

2.  Once erected in the field, all weld seams, plate edges, stand-backs and areas subject to mechanical damage shall be prepared in accordance with eitherSSPC-SP2, SSPC-SP3, SSPC-SP10 or SSPC-SP11. The appropriate surface preparation shall be decided by the owner’s representative.

3.  Prepared areas will require a firm featheredge at coating transitions.

4.  All pre-primed steel must be clean and free from contaminants before coating.

5.  The applicator shall apply two spot prime coats of Macropoxy 646, Intergard 345 Epoxy or Carboguard 60 at 4.0-6.0 mils dry film thickness per coat to the prepared areas.

6.  Safety cages, ladders, top handrails of stairways and platforms, bumper posts, curbs and fencing around transformers shall receive a finish coat of Acrolon 218 ANSI Safety Yellow or Interthane 990HS ANSI Safety Yellow or Carbothane 134HG Safety Yellow in place of the finish coat.

7.  Fire hydrants and monitors, hose racks, foam lines, foam generating equipment and foam storage tanks shall receive a finish coat of Acrolon 218 ANSI Safety Red or Interthane 990HS ANSI Safety Red or Carbothane 134 HG Safety Red in place of the finish coat.

8.  Stencils/Labels shall be Acrolon 218 Black or Interthane 990HS Black or Carbothane 134HG Black.

9.  Ethanol Tanks should use a Mildewcide, such as, Carboline M-1 Advanced Additive (or SW or IP equivalent) in the topcoat layer to deter staining.

CHART 2: New or Existing Steel (Field Applied Primer, Intermediate and Finish Coats)

SURFACE PREPARATION: All surfaces to be coated shall be free from grease and oil; solvent cleaning as per SSPC-SP1 may be required. All new steel shall be abrasive blasted to SSPC-SP10 Near-White Blast Standard with a minimum sharp angular profile of 2.0-3.0 mils. All mill scale must be completely removed. All surfaces that have been previously coated shall be abrasive blasted to SSPC SP6 Commercial Blast Standard with a minimum sharp angular profile of 2.0 mils. Prepared surfaces must be primed within eight hours of blasting or before flash rusting occurs. All published environmental conditions and recoat windows must be followed.
Coat / Product Name / Volume Solids / Recommended Min / DFT Range Max / Coverage (sq.ft./gal) Theoretical No Loss
1st / (Primer)
(SW) Macropoxy 646 Fast Cure Epoxy
(C) Carbguard 60 Epoxy
(IP) Interseal 670 HS Epoxy / 72%
72%
82% / 4.0
4.0
4.0 / 6.0
6.0
4.0 / 192-288
192 – 288
219-328
2nd / (Intermediate)
(SW) Macropoxy 646 Fast Cure Epoxy
(C) Carbguard 60 Epoxy
(IP) Interseal 670 HS Epoxy / 72%
72%
82% / 4.0
4.0
4.0 / 6.0
6.0
4.0 / 192-288
192 – 288
219-328
3rd / (Field Applied Finish)
(SW) Epolon 7 HS Porcelain White
(C) Carboguard 893SG Tank White
(IP) Intergard 1033 Tank White Epoxy
(See notes below) / 63%
63%
62% / 2.0
2.0
2.0 / 4.0
4.0
4.0 / 265-400
265 – 400
249-498

Notes (Chart 2):

1. Safety cages, ladders, top handrails of stairways and platforms, bumper posts, curbs and fencing around transformers shall receive a finish coat of Acrolon 218 ANSI Safety Yellow or Interthane 990 HS ANSI Safety Yellow or Carbothane 134HG ANSI Safety Yellow in place of Epoxy finish coat.

2. Fire hydrants and monitors, hose racks, foam lines, foam generating equipment and foam storage tanks shall receive a finish coat of Acrolon 218 ANSI Safety Red or Interthane 990 HS ANSI Safety Red or Carbothane 134HG ANSI Safety Red in place of the finish coat.

3. Stencils/Labels shall be Acrolon 218 Black or Interthane 990 HS Black or Carbothane 134HG Black.

4. Ethanol Tanks should use a Mildewcide, such as, Carboline M-1 Advanced Additive (or SW or IP equivalent) in the topcoat.

CHART 3: Existing Steel (High Pressure Water Wash Surface Preparation)

SURFACE PREPARATION: Note: this section only applies to recoating surfaces that have been previously blasted and painted. All surfaces to be coated shall be free from grease and oil; solvent cleaning as per SSPC-SP1 may be required. All surfaces to be coated shall be high pressure water washed at 3,000-5,000 PSI with a rotating tip to remove all loose or peeling coating, debris, dirt and contamination. Failed and delaminating existing coatings or corroded shall be prepared in accordance with SSPC-SP2/SP3 Hand Tool/Power Tool Cleaning. Glossy areas may require abrasion to promote coating adhesion. All coating termination will require a firm featheredge in accordance with SSPC-SP/SP3 Hand Tool / Power Tool Cleaning Standards. All published environmental conditions and recoat windows shall be followed.
Coat / Product Name / Volume Solids / Recommended Min / DFT Range Max / Coverage (sq.ft./gal) Theoretical No Loss
1st / (Primer)
(SW) Macropoxy 920
Rust Penetrating Epoxy Pre-Primer
(C) Rustbond Penetrating Sealer
(IP) Interbond 600 Epoxy Sealer / 100%
99%
85% / 1.5
1.0
1.5 / 2.0
2.0
2.0 / 800-1,050
786 – 1572
682-909
2nd / (Intermediate)
(SW) Macropoxy 646 Fast Cure Epoxy
(C) Carbguard 60 Epoxy
(IP) Interseal 670 HS Epoxy / 72%
72%
82% / 4.0
4.0
4.0 / 6.0
6.0
6.0 / 192-288
192 – 288
219-328
3rd / (Field Applied Finish)
Epolon 7 HS Porcelain White
Carboguard 893SG Tank White
(IP) Intergard 1033 Tank White Epoxy
(See notes below) / 63%
63%
62% / 2.0
2.0
2.0 / 4.0
4.0
4.0 / 265-400
265 – 400
249-498

Notes (Chart 3):

1. Safety cages, ladders, top handrails of stairways and platforms, bumper posts, curbs and fencing around transformers shall receive a finish coat of Acrolon 218 ANSI Safety Yellow or Interthane 990 HS ANSI Safety Yellow or Carbothane 134HG Safety Yellow in place of the finish coat.

2. Fire hydrants and monitors, hose racks, foam lines, foam generating equipment and foam storage tanks shall receive a finish coat of Acrolon 218 ANSI Safety Red or Interthane 990 HS ANSI Safety Red Carbothane 134HG Safety Red in place of the finish coat.

3. Stencils/Labels shall be Acrolon 218 Black or Interthane 990 HS Black or Carbothane 134HG Black.

4. Pre-finished new or relocated equipment such as pumps, motors, valves, actuators, etc. are also covered under this specification but do not require the power washing procedure.

5. Valve stems, relief valves, lightning arrestors, instrumentation, mechanical moving parts, etc. shall be properly masked and protected before sandblasting and painting adjacent surfaces.

6. Ethanol Tanks should use a Mildewcide, such as, Carboline M-1 Advanced Additive (or SW or IP equivalent) in the topcoat.

4.0 INSPECTION

4.1  Coating work shall be inspected and accepted by the Owner's Representative. In general the inspection shall include, but not limited to the following activities:

1.  Protection of equipment and areas not to be coated.

2.  Surface preparation and cleanliness.

3.  Surfaces checked for chemical contamination.

4.  Determine and document daily ambient conditions.

5.  Material mixing and/or thinning requirements.

6.  Coating application and maintaining thickness requirements.

7.  Coating repair and clean-up.

8.  Documentation and coating inspection reports.

4.2  Coating defects, including improper surface preparation, incorrect dry film thickness, discontinuities, overspray, runs, sags, entrapped foreign matter, and other coating defects shall be repaired by the Painting Contractor at no additional charge to the Owner.

5.0 LABELING, DECALS, AND STENCILS

5.1  Storage tank numbers shall be twelve-inch (12") high numerals, either decals or stencils, with the top of the numeral located up one-third of the shell height, and viewed from the primary access/egress point.

5.2  All other labels, if required and unless specified otherwise, shall be two-inch (2") high decals or stencils.

5.3  Some local jurisdictions may also require the installation of the NFPA 704 colloquial fire diamond sticker which is used by emergency personnel to identify risks associated with the stored product in the tank.

SURFACE PREPARATION STANDARDS

The basic standards for preparing metal substrates are a joint effort between the Society for Protective Coatings (SSPC) and the National Association of Corrosion Engineers International (NACE).

SSPC-SP1 Solvent Cleaning

Removal of all visible oil, grease, soil, drawing and cutting compounds, and other soluble contaminants from steel surfaces with solvent, vapor, cleaning compound, alkali, emulsifying agent, or steam.

SSPC-SP2 Hand Tool Cleaning

Removes all loose mill scale, loose rust, loose paint, and other loose detrimental foreign matter by hand chipping, scraping, sanding, and wire brushing.

SSPC-SP3 Power Tool Cleaning

Removes all loose mill scale, loose rust, loose paint, and other loose detrimental foreign matter by power wire brushing, power sanding, power grinding, power tool chipping, and power tool descaling.

SSPC-SP5 / NACE 1 White Metal Blast Cleaning

When viewed without magnification, the surface shall be free of all visible oil, grease, dust, dirt, mill scale, rust, coating, oxides, corrosion products and other foreign matter.

SSPC-SP6 / NACE 3 Commercial Blast Cleaning

When viewed without magnification, the surface shall be free of all visible oil, grease, dust, dirt, mill scale, rust, coating, oxides, corrosion products and other foreign matter of at least 66-2/3% of unit area, which shall be a square 3 in. x 3 in. (9 sq. in.). Light shadows, slight streaks, or minor discolorations caused by stains of rust, stains of mill scale, or stains of previously applied coating in less than 33-1/3% of the unit area is acceptable.

SSPC-SP7 / NACE 4 Brush-Off Blast Cleaning

When viewed without magnification, the surface shall be free of all visible oil, grease, dirt, dust, loose mill scale, loose rust, and loose coating. Tightly adherent mill scale, rust, and coating may remain on the surface. Mill scale, rust, and coating are considered tightly adherent if they cannot be removed by lifting with a dull putty knife.