V-CG-SLI 350
Pos. ) ... pcs.
LED Supply- and Monitoring module acc. to EN 61347-2-13 and EN 62384. Suitable to be mounted in luminaires of insulation class I or II for emergency lighting acc. to EN 60598-2-22 and for the operation in emergency lighting systems acc. to, DIN EN 50172, DIN VDE 0100-560 and DIN V VDE V 0108-100. Acc. to ISO 9001 developed, manufactured and tested.
Special LED-converter for a LED series connection (1-8 LEDs, 350mA) with integrated monitoring module for single luminaire monitoring (without additional data line) and 20 addresses for function monitoring (CEWA GUARD Technology).
Error message in case of: Interruption in the LED series connection or a short circuit at the output terminals.
Safe fault identification even if one LED fails due to Single individual monitoring (SLI technology = Single LED monitoring Intelligence)
Switching modes (maintained/non-maintained and switched emergency luminaires) freely programmable in one circuit without additional data line to the luminaires in conjunction with suitable emergency lighting systems (with STAR-Technology).
Extended ambient temperature area from -40°C to +50°C
Primary side (Data valid for Full-Load with 8 LEDs):
Voltage: 220 - 240 V, 50/60 Hz /176 - 275 V DC
Standby power loss: < 0.5 W (230 V / 50 Hz)
Current consumption
battery operation (220V) DC: 43 mA
Power Input:
(Apparent power/ Active power) 11,6 VA / 10,7 W
Power factor: 0,9
Inrush current: ≤ 3,0 A
Operating frequency: 30 kHz – 450 kHz
Connecting terminals: Plug-in terminals 2.5 mm² / reverse-polarity protected
Secondary side:
Output current: 350 mA (constant current) + / - 10%
Output voltage: 30 V DC (open-circuit operation) / 25 V (8 LEDs)
Lamp load: LED series connection (1-8 LEDs; rated current 350 mA;
UFmin = 2.85V / UFmax = 3.12V per LED)
Output power: 8,75 W (max.)
Connecting terminals: Plug-in terminals 1.5 mm² / not reverse-polarity protected
Luminous flux at the end of
Rated operating time EBFL: 100%
Lamp start: ≤ 500 ms
Max. distance
Module / LED: 0,5 m
Degree of protection: IP 20
Ambient
temperature range ta: -40°C up to +50°C
Max. permissible
test point temperature tc: 70°C
Dimensions (mm): L = 110; W = 30; H = 21
Enclosure material / colour: flame-retardant polycarbonate / grey
Module with ENEC-compliance, certified by an independent testing laboratory.
Type: V-CG-SLI 350
Manufactured by: EATON