Flo-Rite-Temp Model 415PP-PR Instantaneous Water Heater Package

Category: Instantaneous Water Heater Package

Type: Flo-Rite-Temp

Model: 415PP-PR

General:

The parallel instantaneous water heater package shall be mounted on an angle iron frame. The package shall be pre-plumbed for both simultaneous and redundant operation with all required components and pressure tested. Packages which require field assembly other than basic water, and steam service shall be unacceptable. The instantaneous water heater shall operate on water differential using the feed forward principle and shall not use a feedback temperature control device with capillary system. The tube bundle shall be fixed on one end and free floating on the other for easy removal. The tubes shall be straight with a removable end cap to facilitate cleaning. “U” and helical tubes shall be unacceptable. The water controlling valve shall be mounted integral to the heat exchanger without the use of connecting piping. Only the necessary steam, water and condensate connections to the instantaneous water heater shall be pre-plumbed. Copper line storage tanks shall not be used.

Materials of construction and items included shall be:

1. Shell of carbon steel with 2” NPT steam inlet and 3/4” NPT condensate exit ports

2. Tubes of 5/8” 16 gauge admiralty brass expanded into brass tube sheets

3. Water control valve body of bronze with stainless steel internals and having 1” NPT water connections for each heater

4. Stand of 2” Carbon Steel Angle

5. Water pipe of Type L copper

6. Armstrong Steam Trap model 812 for each water heater

7. Armstrong Thermostatic Air Vent for each heater

8. All required valve fittings and isolation valves, three way diverting valve, inlet/return check valves, inlet, system blend and return line thermometers

Performance:

The instantaneous water heater shall be of the horizontal shell and tube design providing easy access to the individual tubes without moving the heater from its installed position. No overhead clearance shall be required for servicing. The control valve shall fail in a closed position and shut-off hot water flow. Model shall be Flo-Rite-Temp Model 415PP-PR by Armstrong Hot Water Group, Three Rivers, Michigan.

The parallel instantaneous water heater package shall include all of the following capabilities:

1. Maximum water pressure drop not exceeding 10 psi

2. Accurate control of blended water drawn from the system at a point of use within +/-5°F

3. Operational steam pressure of 2-15 psig

4. Maximum allowable steam pressure of 150 psig

5. Operational water pressure of 20-150 psig

6. Maximum allowable water pressure of 150 psig

Armstrong Hot Water Group, 221 Armstrong Blvd., Three Rivers, MI 49093 – USA Phone: (269) 279-3602 Fax: (269) 279-3130
www.armstronginternational.com