Essentials of Firefighting (4th Edition)
Chapter 15-Sprinkler Systems
FF1 Test Review
What does AUTOMATIC SPRINKLER PROTECTION consist of?
- series of sprinklers (sprinkler heads) arranged so that the system will automatically
- distribute sufficient quantities of water directly to a fire to extinguish it or hold it in check until fire crews arrive
What are the 2 general TYPES of sprinkler coverage?
- Complete Sprinkler System – protects entire building
- Partial Sprinkler System – protects only certain areas such as high-hazard areas, exits, or places designated by code
What are the STANDARDS covering sprinkler systems?
- NFPA 13 – covers installation of sprinklers
- NFPA 13D – covers installation in residential homes, such as 1 & 2 family dwellings and manufactured homes
What does the NFPA standards on sprinklers cover?
- spacing, piping sizes, method of hanging pipe, and all other details of installation
What is the DESIGN of a sprinkler system based on?
- the assumption that only a portion of the sprinklers will operated during a fire
Where should sprinklers and sprinkler parts be LISTED?
- with a nationally recognized testing laboratory such as Underwriters Laboratory or Factory Mutual
What are some reasons a sprinkler system may FAIL?
- partially or completely closed main water control valve
- interruption of municipal water supply
- damaged or painted over sprinklers
- frozen or broken pipes
- excess debris or sediment in pipes
- failure of a secondary water supply
- tampering or vandalism
Why is LIFE SAFETY enhanced by sprinkler systems?
- they discharge water directly on a fire while it is relatively small
- because fire is extinguished or controlled during early growth stage, combustion products are limited
In what situations can sprinklers be EFFECTIVE?
- preventing fire spread upwards in multi-story buildings
- protecting lives of occupants in other parts of building
When are sprinklers alone NOT as EFFECTIVE?
- When fires too small to activate sprinklers
- When smoke generation reaches occupants before activating sprinklers
- When sleeping, intoxicated, or handicapped persons occupy the fire building
What COMPONENTS are attached to the RISER (vertical piping)?
- sprinkler valve, one-way check valve, fire department connection (FDC), alarm valve, and main drain
What is a FEED MAIN?
- pipe connecting the riser to the cross mains
What does a CROSS MAIN do?
- directly service a number of branch lines on which the sprinklers are installed
- extend past the last branch and are capped to facilitate flushing
What happens to PIPING SIZE throughout the system?
- pipe size decreases from the riser outward
How do sprinklers operate?
- they discharge water after a release of a plug or cap that is activated by a heat-sensitive element
- can be thought of as a fixed-spray nozzle operated by a thermal detector
How are sprinklers identified?
- by the temperature at which they are designed to operate
- either by color coding the sprinkler frame arm, by using different colored liquid in bulb sprinklers, or by stamping temperature into sprinkler
What are the 3 most common RELEASE MECHANISMS?
- Fusible Link – frame screwed into sprinkler piping with 2 levers pressing against frame and a cap over orifice to hold back water.
- Frangible Bulb – small bulb filled with liquid and an air bubble hold orifice shut, heat expands liquid until bulb shatters.
- Chemical Pellet – a pellet of solder under compression within a small cylinder melts at a predetermined temperature allowing plunger to move down and release water
What is a QUICK-RESPONSE MECHANISM?
- a specially designed fusible link sprinkler with a low tolerance to heat generated by a fire
- a quick opening sprinkler was developed for life safety
How is the BREAKING TEMPERATURE regulated in frangible bulb sprinklers?
- by the amount of liquid and the size of the bubble in the bulb
- liquid is color coded to designate breaking temperature
What are the 3 basic POSITIONS for sprinklers?
- Pendant – (MOST COMMON) extends down from underside of piping, sprays water downward into a deflector that breaks the stream into a hemispherical pattern
- Upright – sits on top of piping, sprays water into a solid deflector that redirects water in a hemispherical pattern toward the floor
- Sidewall – extends from the side of a pipe, used in small rooms where branch lines run along wall. Deflector creates a fan shape pattern of water
What are SPECIAL-PURPOSE sprinklers?
- those used in specific applications because of unique characteristics (recessed, corrosive resistant, etc)
What items should be found in a STORAGE CABINET?
- a MINIMUM of 6 (six) sprinklers and a sprinkler wrench
- sprinklers should be changed by qualified representatives
What are CONTROL VALVES used for?
- to turn OFF the water supply so that sprinklers may be replaced, maintenance can be performed, or operations can be interrupted
- located between the water source and the sprinklers
- usually located immediately under the sprinkler alarm valve, the dry-pipe or deluge valve, or outside the building near the sprinkler system it controls
- ALWAYS return to the open position after maintenance is complete
What must be done to insure valves do not INADVERTENTLY close?
- valves should be supervised or secured in the open position
What is an INDICATING CONTROL VALVE?
- one that shows at a glance whether it is open or closed
What types of valves are found on the MAIN WATER CONTROL?
- indicating and manually operated
What are the four common types of VALVES used in sprinkler systems?
- OS&Y (Outside Screw and Yoke) – has a yoke on the outside with a threaded stem
- Post Indicator Valve (PIV) – hollow metal post attached to the valve housing, the words OPEN and SHUT are printed at the opening
- Wall Post Indicator Valve (WPIV) – PIV that extends through the wall with a target and valve operating nut on the outside of the building
- Post Indicator Valve Assembly (PIVA) – does not use the words OPEN and SHUT, but has a sight area that is open when valve is open and closed when valve is closed
What are the OPERATING VALVES used in sprinkler systems?
- alarm test valve, inspector’s test valve, and a main drain valve
What is the RETARD CHAMBER?
- place that catches excess water from momentary water pressure surges
Where is the ALARM TEST VALVE located?
- on a pipe that connects the supply side of the alarm check valve to the retard chamber
- provided to stimulate the actuation of the system by allowing water to flow into the retard chamber and operate the water flow alarm devices
Where is the INSPECTOR’S VALVE located?
- in a remote part of the sprinkler system
- equipped with same size orifice as one sprinkler and is used to stimulate the activation of one sprinkler
- should drain to the outside of the building
What is the PRIMARY PURPOSE of the MAIN DRAIN VALVE?
- to simply drain water from the system for maintenance purposes
- can also be used to check the system water supply
How are WATER FLOW ALARMS operated?
- hydraulically or electrically by flowing water
- alerts personnel of flowing water in the system
- water from a branch of the system is fed into a water motor that drives a local alarm gong
- can also be arranged to notify fire department as well as occupants
What must a MINIMUM WATER SUPPLY deliver?
- to deliver the required volume of water to the highest sprinkler in the system at a residual pressure of 15 psi
- minimum flow depends on hazard to be protected, its occupancy, and building contents
What is the water supply DESIGNED TO SUPPLY?
- only a fraction of the sprinklers in the system
What happens if a LARGE FIRE or PIPE BREAK occurs?
- system will need an outside source of water and pressure to effectively do its job
How is ADDITIONAL PRESSURE provided to a system?
- a pumper connected to the Fire Department Connection (FDC) to boost flow
What do FIRE DEPARTMENT CONNECTIONS (FDC) consist of?
- usually a siamese with at least two 2 1/2-inch female connections with a clapper valve or one large diameter connection that is connected to a clappered inlet
- pumpers supplying FDC’s should have a capacity of AT LEAST 1,000 gpm
- a minimum of two 2 1/2-inch or larger hoses should be attached to the FDC
What hydrants should pumpers use to BOOST FD CONNECTIONS?
- Hydrants connected to a main other than the one supplying the sprinkler system
What does a CHECK VALVE do?
- prevents water from system from entering FDC
- prevent water coming into the FDC from entering sprinkler system directly
What is a BALL DRIP VALVE?
- keeps the check valve dry and from freezing
What should FD SOP’s include for sprinklered buildings?
- identify operating pressures for systems
- types of occupancies
- types of systems
- extent of the systems
What are important factors when fighting fire in a sprinklered building?
- early arriving pumper should attach to FDC
- sprinkler pressure should be first priority
- limit hoselines from same water supply as sprinkler system
- system control valves must be open
- sprinklers should not be closed until fire officer deems water is being wasted, producing heavy water damage, or hamper final extinguishment by FF’s
- premature closure of control valve could result in increased intensity of the fire
- a FF should be stationed at a closed control valve in case reopening because of a rekindle is necessary
- pumpers should not disconnect from FDC until extinguishment and overhaul is complete
- sprinklers systems should be restored to service before leaving premises
- system maintenance should be performed by a representative of the occupant
- for liability purposes, FF personnel should not service sprinklers
Why would it be necessary to STOP THE FLOW of a sprinkler?
- residual water after the main valve is closed will continue to drain through an open sprinkler
How should the flow of water be STOPPED in a sprinkler?
- by using wooden wedges or commercially made stoppers in between the orifice and deflector