Section 26 53 00

Ecoglo PhotoluminescentExit Signs

This specification has been numbered, organized and formatted in accordance with the MasterFormat, Section Format and Page Format documents published jointly by Construction Specifications Institute (CSI). For convenience, all products are contained within Section 26 53 00 (PhotoluminescentExit Signs) but if desired may be edited/adapted to suit any other Section(s) of Work in accordance with project requirements.

It is offered as a guide to experienced and knowledgeable construction professionals who assume full responsibility for its interpretation and use. Square brackets [ ] containing text indicate an option to be considered/inserted by the specifier. Remove brackets and unused options before printing.

Ecoglo products are designed to provide path finding and emergency egress for building occupants of all abilities, and may be used to supplement electrical emergency lighting.

This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as hidden text, and can be revealed or hidden by one of the following methods:

  • Microsoft Word 2007: Click the OFFICE button, select WORD OPTIONS, select DISPLAY, and then select or deselect the HIDDEN TEXT option.
  • Microsoft Word (earlier versions): From the pull-down menus select TOOLS, then OPTIONS. Under the tab labeled VIEW, select or deselect the HIDDEN TEXT option.
  • Corel WordPerfect: From the pull-down menus select VIEW, then select or deselect the HIDDEN TEXT option.

Section 26 5300

PhotoluminescentExit Signs

Part 1General

1.1Summary

AWork Included: Furnishing and installation of photoluminescent exit signs.

1.2References

A[National Fire Protection Association (NFPA) 101 - Life Safety Code]
[International Building Code / International Fire Code (IBC/IFC)]

BUL 924, Standard for Emergency Lighting & Power Equipment

1.3Quality Assurance

AManufacturer Qualifications:to have minimum of 10 years experience with similar work.

BInstaller Qualifications:to be manufacturer trained/authorized installer.

1.4Submittals

ASubmit the following [in accordance with Section 01 33 00 – Submittal Procedures]:

1Product Data:Manufacturer’s printed product literature for materials used in system.

2Shop Drawings:Provide CAD drawings showing details, dimensions, extent of work, and other data necessary for the satisfactory installation of the products stated herein.

3Manufacturer’s Instructions:Pre-printed material describing installation of product, system or material, including special notices and Material Safety Data Sheets outlining hazards and safety precautions.

4Test Reports: Showing compliance with required standards, ordinances and codes.

5Substitutions: Not permitted, however requests for substitutions will be considered provided substitute products and methods of execution are submitted at least 15 days prior to the bid closing date. All requests shall include test results, product descriptions, confirmation of piece design and engineering calculations meeting design criteria.

1.5Delivery, Storage and Handling

AHandle and store Products in a manner to prevent damage, deterioration and soiling to Products, other building components, assemblies, other Products, the structure, the Site and surrounding property and in accordance with manufacturer’s instructions.

BStore packaged or bundled Products in original and undamaged containers and packaging with manufacturer’s seals and labels intact.Do not remove from packaging or containers until required in the Work.

CStore products subject to damage from weather in weatherproof enclosures.

1.6Warranty

AProvide a written and signed Warranty in the name of the Owner for a period of fifteen (15) years from the date of Substantial Performance of the Work.

BWarranty to cover defects in materials and workmanship.

Part 2Products

2.1Manufacturers

AContract Documents are based on products by Ecoglo Inc. (

BSubstitutions: [Under provisions of Division 01.] [Not permitted.]

2.2Materials

AReflectancematerial: strontium aluminate-based photoluminescentpigment embedded in thermoset polyester carriers that integrally bond the active ingredients into powdercoated aluminum substrates following curing at 350°F (180°C).

BFrame and mounting components: 6060T5 aluminum clear anodized to Class 1, .0007” (20 microns) thickness.

2.3Components

ABasis of design: Ecoglo EX SeriesPhotoluminescent Exit Sign System

1Description:

  1. Stores energy from ambient fluorescent, metal halide or mercury vapor light
  2. Non-toxic, non-radioactive
  3. UL 924 Listed
  4. [Aluminum frame and universal mounting kit]
  5. [Red] [Green] print on photoluminescent background

BMounting type: [Ceiling] [Sloped ceiling] [Flag] [Surface] [Canopy retro-fit],[As per Schedule attached at end of Section] [As indicated in drawings]

CVisibility rating: [50 feet]

SPEC NOTE: The listed italics data included below provide product codes, colors, designations and dimensions for comparison purposes. Specification articles (product selections) contained within square brackets [ ] are shown as example choices only.

Product Code / Frame / Sides / Color of print / Rated visibility / Dimensions
EX405229-75R / w/o / Single / Red / 75 feet / 18.9” x 9.8” (481 mm x 249 mm)
EX405229-75G / w/o / Single / Green / 75 feet / 18.9” x 9.8” (481 mm x 249 mm)
EX424246-75R-CA / w/ / Single / Red / 75 feet / 19.6” x 10.5” (499 mm x 267 mm)
EX424246-75G-CA / w/ / Single / Green / 75 feet / 19.6” x 10.5” (499 mm x 267 mm)
2X-EX424246-75R-CA / w/ / Double / Red / 75 feet / 19.6” x 10.5” (499 mm x 267 mm)
2X-EX424246-75G-CA / w/ / Double / Green / 75 feet / 19.6” x 10.5” (499 mm x 267 mm)
EX353183-50R / w/o / Single / Red / 50 feet / 13.9” x 7.2” (353 mm x 183 mm)
EX353183-50G / w/o / Single / Green / 50 feet / 13.9” x 7.2” (353 mm x 183 mm)
EX371201-50R-CA / w/ / Single / Red / 50 feet / 14.6” x 7.9” (371 mm x 201 mm)
EX371201-50G-CA / w/ / Single / Green / 50 feet / 14.6” x 7.9” (371mm x 201 mm)
2X-EX371201-50R-CA / w/ / Double / Red / 50 feet / 14.6” x 7.9” (371 mm x 201 mm)
2X-EX371201-50G-CA / w/ / Double / Green / 50 feet / 14.6” x 7.9” (371 mm x 201 mm)

Part 3Execution

3.1Examination

ABefore installation, examine surfaces on which the Work of this Section depends.Notify [Contractor] if surfaces do not comply with requirements of this Section

BDo not proceed with Work of this Section until all unsatisfactory conditions have been corrected, if any.

CCommencement of Work will imply acceptance of surfaces.

3.2Preparation

AClean surfaces to remove debris, dirt, dust, grease, oil, loose material, or other matter that may affect installation of photoluminescent products.

3.3Installation

AInstall signs [as per Schedule attached at end of Section] [as indicated in Drawings].

BUnless otherwise indicated in the specifications, install Products in accordance with manufacturer’s instructions.Obtain written instructions directly from manufacturer.

3.4Cleaning

AAt completion of installation, clean soiled Product surfaces in accordance with manufacturer’s instructions.

3.5Waste Management and Disposal

ASeparate waste materials for [reuse] [and] [recycling] at nearest used building materials facility.

3.6Protection

ADo not allow heavy objects to come in contact with installed products.

3.7Products/Signage Schedule

Sign Designation / Sign Type / Mounting Type
[Sign designation on drawing] / [EX353183-50R] / [Surface]
[Sign designation on drawing] / [2X-EX371201-50R-CA] / [Flag]

End of Section