DT231/2 Control and Instrumentation MiniProject

Student : Alan Sherry

Date : 17/December/2003

Lecturers : Ciaran Young & Gavin Duffy

INTRODUCTION:

For this project an electronic temperature sensing instrument was successfully designed and built using VERO board.

An RTD was used as a transducer to transform ambient temperature into an electrical signal. The RTD used in this experiment consisted of a platinum winding encased within a stainless steel sleeve. This signal was then conditioned using a wheatstone bridge to give an output range of 0 to 100 mV.

This works because an RTD transforms temperature applied to it into a proportional change in resistance and the signal conditioning circuit can be used to scale this output into a more easily readable output signal.

This is described in block diagram form below.

The required linear output was successfully obtained in the ranges as follows :

Output Range : 0 to 100 mV

Input Temperature Range: 0 °C to 100 °C.

An RTD (Platinum resistance Wire) Temperature Sensor RTD100 was used as the temperature sensing element . RTD sensors generate output signals in one of two ways: through a change in output voltage or through a change in resistance of the sensor's electrical circuit. The Platinum RTD, Resistance Temperature Detector is one of the most linear, stable, and reproducible temperature sensors .An RTD’ resistance vs temperature characteristics are stable, reproducible, and have a near linear positive temperature coefficient from 200 to 800 °C.

These attributes establish RTDs as a de-facto industry standard and it was for this reason that I wanted to have an RTD in my project even though the time constant is longer than it would be for a thermocouple.

It was decided to input a supply voltage of 15 Volts into the WHEATSTONE BRIDGE signal conditioning circuit .In this case ,it was not required to build a linear amplifier to obtain the desired output range .If one had been required I could have chosen to condition the output of the wheatstone bridge with an instrumentation amplifier using UA741 OP AMPS or even a differencing amplifier .

In such an event the output of the amplifier would have to be within the saturation range which for a UA741 is approximately +-15 Volts

The resistance of the RTD increases with temperature and in such circumstances a corresponding proportional increase in voltage is detected at the wheatstone bridge output .

The RTD Temperature Circuit was tested in the environment of the lab using beakers of boiling and warm water and also using a beaker of ice and icy water .

The RTD was wired into the signal conditioning circuit ( a wheatstone bridge used as a deflection bridge) and was brought into contact with temperatures over the required range .

Design:

When building my temperature sensor, I had different choices available to me (Thermocouple or thermistor with their different advantages and disadvantages). I had to consider the different constraints imposed by different design systems.

Below is an outline of the design of an RTD. As I choose to use an RTD for the project , I will only briefly mention other types of sensors.

RTDs:

These are precision temperature-sensing devices. They're the ones to use when applications require accuracy, long-term electrical (resistance) stability, element linearity, and repeatability. The devices can work in a wide temperature range—some platinum sensors handle temperatures from 328ºF to 1202ºF.

The sensing element in RTDs is typically a fine platinum wire winding or thin metallic layer applied to a ceramic substrate. The platinum resistance thermometer is the primary interpolation instrument used by the National Bureau of Standards in applications with operating temperature ranges from 436ºF to 1135ºF.

RTDs as a class are divided into two types:

  • Resistance wire RTD
  • Thermistor (thermally sensitive transistor)

RTDs work by producing a predictable resistance at a given temperature. Resistance wire RTDs (generally platinum) have a positive coefficient by increasing resistance with temperature increase. The resistance of most metals increases reasonably linearly with temperature in the range –100°C to 800 °C. This is the physical principle the instrument is based on. Nickel, copper and platinum are the main materials used .

Platinum has the most linear characteristic over the widest range and thus is the most desired and the most expensive. Thermistors are generally negative coefficient by decreasing resistance with temperature increase.

Some of the advantages for choosing the RTD for the lab experiment are set out below:

RTD Advantages:

They are possessed of a wide temperature range for example , Watlow Gordon platinum sensors cover temperatures from -328 to 1202°F (-200 to 650°C),with repeatability and stability: The platinum resistance RTD is the primary interpolation instrument used by the National Bureau of Standards from -436 to 1135°F (-260 to 630°C). Precision RTDs can be manufactured with stability of 0.0025°C per year. Industrial models typically drift less than 0.1°C per year.

They have a high output ( The current drop across an RTD provides a much larger signal than thermocouple voltage output) and linearity of output (extremely important for this project, platinum and copper element RTDs follow a more linear curve than thermocouples or most thermistors).

They have a low system wiring cost. Unlike a thermocouple, an RTD uses ordinary copper leads for extension wires and requires no cold junction compensation.

The coils inside the stainless steel sleeve of the RTD take advantage of area averaging for temperature response. Point measurements, while often desirable, may cause errors. An RTD element can be spread over a large area, improving control with area averaging, a technique impractical with thermocouples.

Precision thermometers can be manufactured with stability of 0.0025ºC per year. However, industrial models typically drift < 0.1ºC per year. RTDs with platinum and copper elements follow a more linear curve than thermocouples or most thermistors. Unlike a thermocouple, an RTD uses copper wire products for instrument connection and requires no cold junction compensation. As a result, system cost is often lower.

Although point measurements are often desirable, they can cause errors. An RTD element can be spread over a large area, improving control with area averaging, an impractical technique with thermocouples. The voltage drop across an RTD provides a much larger signal than thermocouple voltage output.

Effects of Leadwire Resistance :
Because the RTD is a resistive device, any resistance elsewhere in the circuit will cause errors in the readings for the sensor. The most common source of additional resistance is in the leadwires attached to the sensor, especially with assemblies that have long extension leads as part of the assembly. The amount of error introduced into the system will depend upon the length and AWG of the wire as well as the base resistance value of the RTD. Leadwire error can be significant, especially with long runs of small diameter leads or low resistance elements. The use of a 3-wire or 4-wire system will reduce errors to negligible levels in most applications. The need for a 3-wire or 4-wire system will be dependent upon the resistance value of the sensing element, the length and AWG of the leadwires as well as the accuracy required.

The drawbacks to this sensing technology are slower response time (40 seconds recorded for this project, due to large element size), sensitivity to shock and vibration, small resistance change (low sensitivity) for temperature variations, and low base resistance. Low base resistance and small resistance change for corresponding temperature change become a concern when long lead lengths are required because the leads create additional resistance. When added to the resistance of the RTD element, the lead resistance can result in measurement errors. To overcome lead-length problems, you should use 3- or 4-wire lead circuitry; this allows the effect of a bridge circuit to measure the resistance change based on temperature. Wire-length errors are minimized because the resistance change occurs at the RTD sensing point. Accuracy of the measurement is primarily dependent on the accuracy of the signal conditioning circuit in the controller or measuring device.

An RTD can be classified as a contact sensor. It is designed to be a platinum coil contained within a stainless steel sleeve.

Contact Temperature Sensor Types :RTD

There are two methods of temperature sensing: contact and noncontact. Contact sensing brings the sensor in physical contact with the substance or object being measured; you can use this approach with solids, liquids, or gases.

This was the approach taken in the laboratory when the RTD was brought into contact with ice and boiling water .

RTDs are best for most industrial measurements over a wide temperature range, especially when sensor stability is essential for proper control.

Now to explain the operation of the signal conditioning circuit i.e the deflection bridge:

Wheatstone Bridge Background

A wheatstone bridge is an electrical circuit for the precise comparison of resistances. It is a DC device and can also be used as a deflection bridge as in this project where

it was used to modify a change in resistance to a change in voltage which could be more easily be used for display purposes.

It consists of a common source of electrical current (such as a battery) and a galvanometer that connects 2 parallel branches, containing 4 resistors, three of which are known .

A current flows in an electrical circuit driven by the potential difference at the battery. Resistance, current and voltage are connected by Ohm's law
U=RI
where U is the voltage, R the resistance and I the current.

The current and potential difference (= measured voltage) in each part of the circuit can be calculated with the help of Kirchhoff's rules

  1. The sum of the potential drops around any circuit loop must equal the sum of the potential increases
  2. At a junction point in a circuit where the current can divide, the sum of the currents into the junction must equal the sum of the currents out of the junction.

Look at the following setup: This is an example of a wheatstone or deflection bridge:

The potential drop across the multimeter is zero if
I1*R1=I3*Rx and
I2*R2=I4*R4
and as the potential drop over the galvanometer is zero, so is the current and we have
I1=I2 and
I3=I4
With this equation we see that the unknown resistance is given by
Rx=(R1/R2)*R4

For this experiment a wheatstone bridge was used as a deflection bridge in which case 3 resistance values were fixed and not adjusted and the output voltage varies proportionally as the fourth resistor ,the RTD , changes distance in accordance with its temperature response .