BACnet Protocol Implementation Conformance Statement
S-1 DDC
Date: 16th JAN 2015
Vendor Name: S-1 Corporation
Product Name: S-1 DDC
Product Model Number: EPM-10053
Application Software Version: A01.01.00 Firmware Revision: S01.01.46 BACnet Protocol Revision: 7
Product Description:
S-1 DDC is the controller of S-1 Corporation for Building Automation System. The S-1 DDC provides high-performance. The controller supports B-BC with BACnet-IP and BACnet MS/TP, Gateway function. And, the controller offers modular type installation. The ddc provides superior flexibility. One S-1 DDC supports twenty Input and output modules.
BACnet Standardized Device Profile (Annex L):
oBACnet Operator Workstation (B-OWS)
oBACnet Advanced Operator Workstation (B-AWS)
oBACnet Operator Display (B-OD)
x BACnet Building Controller (B-BC)
oBACnet Advanced Application Controller (B-AAC)
oBACnet Application Specific Controller (B-ASC)
oBACnet Smart Sensor (B-SS)
oBACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K):
BIBB Name / DesignationData Sharing
Data Sharing – ReadProperty – A,B / DS-RP-A,B
Data Sharing – ReadPropertyMultiple – A,B / DS-RPM-A,B
Data Sharing – WriteProperty – A,B / DS-WP-A,B
Data Sharing – WritePropertyMultiple - B / DS-WPM-B
Data Sharing – COV-Unsolicited-A,B / DS-COVU-A,B
Alarm & Event Management
Alarm and Event-Notification Internal-B / AE-N-I-B
Alarm and Event-Acknowledgement - B / AE-ACK-B
Alarm and Event-Information-B / AE-INFO-B
Alarm and Event-Enrollment Summary-B / AE-ESUM-B
Scheduling
Scheduling-Internal-B / SCHED-I-B
Scheduling-External-B / SCHED-E-B
Trending
Trending-Viewing and Modifying Trends Internal-B / T-VMT-I-B
Trending-Automated Trend Retrieval-B / T-ATR-B
Device & Network Management
Device Management – Dynamic Device Binding – A,B / DM-DDB-A,B
Device Management – Dynamic Object Binding – A,B / DM-DOB-A,B
Device Management – DeviceCommunicationControl – B / DM-DCC-B
Device Management-TimeSynchronization-B / DM-TS-B
Device Management-UTCTimeSynchronization-B / DM-UTC-B
Device Management-ReinitializeDevice-B / DM-RD-B
Device Management-Backup and Restore-B / DM-BR-B
Network Management-Connection Establishment / NM-CE-A
Segmentation Capability:
xAble to transmit segmented messages Window Size 1
oAble to receive segmented messages Window Size
Standard Object Types Supported:
Object Type / Dynamically Creatable / Dynamically Deletable / Property / Conformance Code / Optional Property Supported / Writable Property Not Required To Be WritableDevice / o / o
Object_Identifier / R / x
Object_Name / R / o
Object_Type / R / o
System_Status / R / o
Vendor_Name / R / o
Vendor_Identifier / R / o
Model_Name / R / o
Firmware_Revision / R / o
Application_Software_Version / R / o
Location / O / o / o
Description / O / o / o
Protocol_Version / R / o
Protocol_Revision / R / o
Protocol_Services_Supported / R / o
Protocol_Object_Types_Supported / R / o
Object_List / R / o
Max_APDU_Length_Accepted / R / o
Segmentation_Supported / R / o
Max_Segments_Accepted / O / o / o
VT_Classes_Supported / O / x / o
Active_VT_Sessions / O / o / o
Local_Time / O / o / o
Local_Date / O / x / o
UTC_Offset / O / x / x
Daylight_Savings_Status / O / x / x
APDU_Segment_Timeout / O / x / o
APDU_Timeout / R / o
Number_Of_APDU_Retries / R / o
List_Of_Session_Keys / O / o / o
Time_Synchronization_Recipients / O / o / o
Max_Master / O / o / x
Max_Info_Frames / O / x / o
Device_Address_Binding / R / o
Database_Revision / R / o
Configuration_Files / O / o / o
Last_Restore_Time / O / x / o
Backup_Failure_Timeout / O / x / o
Active_COV_Subscriptions / O / x / o
Slave_Proxy_Enable / O / x / o
Manual_Slave_Address_Binding / O / o / o
Auto_Slave_Discovery / O / o / o
Slave_Address_Binding / O / o / o
Profile_Name / O / o / o
Analog Input / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / R / o
Description / O / o / o
Device_Type / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / x
Update_Interval / O / o / o
Units / R / x
Min_Pres_Value / O / o / o
Max_Pres_Value / O / o / o
Resolution / O / o / o
COV_Increment / O / x / x
Time_Delay / O / x / x
Notification_Class / O / x / x
High_Limit / O / x / x
Low_Limit / O / x / x
Deadband / O / x / x
Limit_Enable / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Analog Output / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / W / o
Description / O / o / o
Device_Type / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / x
Units / R / x
Min_Pres_Value / O / o / o
Max_Pres_Value / O / o / o
Resolution / O / o / o
Priority_Array / R / o
Relinquish_Default / R / o
COV_Increment / O / x / x
Time_Delay / O / x / x
Notification_Class / O / x / x
High_Limit / O / x / x
Low_Limit / O / x / x
Deadband / O / x / x
Limit_Enable / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Analog Value / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / W / o
Description / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / o
Units / R / o
Priority_Array / O / x / o
Relinquish_Default / O / x / o
COV_Increment / O / x / x
Time_Delay / O / o / o
Notification_Class / O / o / o
High_Limit / O / o / o
Low_Limit / O / o / o
Deadband / O / o / o
Limit_Enable / O / o / o
Event_Enable / O / o / o
Acked_Transitions / O / o / o
Notify_Type / O / o / o
Event_Time_Stamps / O / o / o
Profile_Name / O / o / o
Binary Input / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / W / o
Description / O / o / o
Device_Type / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / x
Polarity / R / x
Inactive_Text / O / o / o
Active_Text / O / o / o
Change_Of_State_Time / O / o / o
Change_Of_State_Count / O / o / o
Time_Of_State_Count_Reset / O / o / o
Elapsed_Active_Time / O / o / o
Time_Of_Active_Time_Reset / O / o / o
Time_Delay / O / x / x
Notification_Class / O / x / x
Alarm_Value / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Binary Output / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / W / o
Description / O / o / o
Device_Type / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / x
Polarity / R / x
Inactive_Text / O / o / o
Active_Text / O / o / o
Change_Of_State_Time / O / o / o
Change_Of_State_Count / O / o / o
Time_Of_State_Count_Reset / O / o / o
Elapsed_Active_Time / O / o / o
Time_Of_Active_Time_Reset / O / o / o
Minimum_Off_Time / O / o / o
Minimum_On_Time / O / o / o
Priority_Array / R / o
Relinquish_Default / R / o
Time_Delay / O / x / x
Notification_Class / O / x / x
Feedback_Value / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Binary Value / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / W / o
Description / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / x
Inactive_Text / O / o / o
Active_Text / O / o / o
Change_Of_State_Time / O / o / o
Change_Of_State_Count / O / o / o
Time_Of_State_Count_Reset / O / o / o
Elapsed_Active_Time / O / o / o
Time_Of_Active_Time_Reset / O / o / o
Minimum_Off_Time / O / o / o
Minimum_On_Time / O / o / o
Priority_Array / O / x / o
Relinquish_Default / O / x / o
Time_Delay / O / x / x
Notification_Class / O / x / x
Alarm_Value / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Calendar / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Description / O / o / o
Present_Value / R / o
Date_List / R / x
Profile_Name / O / o / o
Event Enrollment / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Description / O / o / o
Event_Type / R / x
Notify_Type / R / x
Event_Parameters / R / x
Object_Property_Reference / R / x
Event_State / R / o
Event_Enable / R / x
Acked_Transitions / R / o
Notification_Class / R / o
Event_Time_Stamps / R / o
Profile_Name / O / o / o
File / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Description / O / o / o
File_Type / R / o
File_Size / W / o
Modification_Date / R / o
Archive / W / o
Read_Only / R / o
File_Access_Method / R / o
Record_Count / O / o / o
Profile_Name / O / o / o
Loop / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / R / o
Description / O / o / o
Status_Flags / R / o
Event_State / R / o
Reliability / O / o / o
Out_Of_Service / R / x
Update_Interval / O / o / o
Output_Units / R / x
Manipulated_Variable_Reference / R / x
Controlled_Variable_Reference / R / x
Controlled_Variable_Value / R / o
Controlled_Variable_Units / R / o
Setpoint_Reference / R / x
Setpoint / R / x
Action / R / x
Proportional_Constant / O / x / x
Proportional_Constant_Units / O / x / o
Integral_Constant / O / x / x
Integral_Constant_Units / O / x / o
Derivative_Constant / O / x / x
Derivative_Constant_Units / O / x / o
Bias / O / o / o
Maximum_Output / O / x / x
Minimum_Output / O / x / x
Priority_For_Writing / R / x
COV_Increment / O / x / x
Time_Delay / O / x / x
Notification_Class / O / x / x
Error_Limit / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Notification Class / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Description / O / o / o
Notification_Class / R / o
Priority / R / x
Ack_Required / R / x
Recipient_List / R / x
Profile_Name / O / o / o
Program / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Program_State / R / o
Program_Change / W / o
Reason_For_Halt / O / o / o
Description_Of_Halt / O / o / o
Program_Location / O / o / o
Description / O / o / o
Instance_Of / O / o / o
Status_Flags / R / o
Reliability / O / o / o
Out_Of_Service / R / o
Profile_Name / O / o / o
Schedule / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Present_Value / R / o
Description / O / o / o
Effective_Period / R / x
Weekly_Schedule / O / x / x
Exception_Schedule / O / x / x
Schedule_Default / R / x
List_Of_Object_Property_References / R / x
Priority_For_Writing / R / x
Status_Flags / R / o
Reliability / R / o
Out_Of_Service / R / x
Profile_Name / O / o / o
Trend Log / o / o
Object_Identifier / R / o
Object_Name / R / o
Object_Type / R / o
Description / O / o / o
Log_Enable / W / o
Start_Time / O / x / x
Stop_Time / O / x / x
Log_DeviceObjectProperty / O / x / x
Log_Interval / O / x / x
COV_Resubscription_Interval / O / o / o
Client_COV_Increment / O / o / o
Stop_When_Full / R / x
Buffer_Size / R / x
Log_Buffer / R / o
Record_Count / W / o
Total_Record_Count / R / o
Notification_Threshold / O / x / x
Records_Since_Notification / O / x / o
Last_Notify_Record / O / x / o
Event_State / R / o
logging-type / R / o
status-flags / R / o
Notification_Class / O / x / x
Event_Enable / O / x / x
Acked_Transitions / O / x / o
Notify_Type / O / x / x
Event_Time_Stamps / O / x / o
Profile_Name / O / o / o
Data Link Layer Options:
xBACnet IP, (Annex J)
oBACnet IP, (Annex J), Foreign Device
oISO 8802-3, Ethernet (Clause 7)
oATA 878.1, 2.5 Mb. ARCNET (Clause 8)
oATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ______
xMS/TP master (Clause 9), baud rate(s): 38400 bps
xMS/TP slave (Clause 9), baud rate(s): 38400 bps
oPoint-To-Point, EIA 232 (Clause 10), baud rate(s):