MAINTENANCE PROCEDURES
for
FACILITY & EQUIPMENT
Revised May 2005
Centre Area Transportation Authority (CATA)
2081 West Whitehall Road
State College, PA 16801
(814) 238-CATA(2282)
MAINTENANCE PROCEDURES for FACILITY & EQUIPMENT
INDEX
Administration Building Cleaning..Page 7
Air Compressor...Page 1
Antifreeze PumpsPage 1
Bus Radios..Page 7
Bus WashPage 1
Computers/PC SystemPage 8
Controls for Heating System..Page 5
Evergreen Beds and Mulching and Weed Control.Page 6
Exhaust Fans...Page 3
Electrical RepairsPage 4
Fire Alarm System..Page 7
Fire Sprinkler System.Page 5
Floor DrainsPage 5
Fuel Lane Pits.Page 1
Fuel Pumps.Page 1
Gas Detection System.Page 2
Generator.Page 5
Ground Maintenance...Page 6
HoistPage 3
Lights and Lighting Inside/Outside....Page 3
Oil PumpsPage 1
Oil Water Separator.Page 4
Overhead Doors..Page 6
Plumbing.Page 8
Pumping Station (CNG)..Page 8
Rapid Air Furnace...Page 3
Roof Flat over Maintenance Bus Storage...Page 7
Roof Shingles on Administrative SidePage 7
Snow RemovalPage 8
Telephones..Page 7
Time Clocks....Page 7
Underground Fuel Tanks and Oil Tanks.Page 6
Water Heaters.Page 5
York Furnace..Page 4
McCarls, Akin Bros., SSI, High Tech Electric reference books reference noted within are located in the Maintenance Supervisor’s office on book case #1, shelf #2.
******************************************************************
Air Compressor See McCarl’s Book, Sec. 1
Daily: Check oil level before it is turned on
Personnel Responsible: AM Open Person
Contact: Emglo Products Corporation
Johnstown Industrial Park
Johnstown, PA 15904
(814) 266-8659
Model #: 2(T25 A or B)
******************************************************************
Oil and Antifreeze Pumps See McCarl’s Book, Sec. 9
Daily: Check for leaks
Personnel Responsible: All Maintenance Persons
Service: (800) 747-5300
Parts: (513) 771-8885
Contact: John Teerters, Rod Johnson Associates
******************************************************************
Fuel Pumps See McCarl’s Book, Sec. 5
Daily: Check for leaks while using
Personnel Responsible: All Maintenance Persons
Contact: Red Jacket Pumps
5800 Foxridge Drive
Mission, KS 66202
(913) 831-5700
******************************************************************
Bus Wash/Fuel Lane Pits/Water Recycle Tanks See SSI Book
Every Six Months: Check pits
Twice a Year: Clean pits
Safety Kleen, (717) 697-9783
Personnel Responsible: All Maintenance Persons
Contact: (Bus Washer) Sherman Supersonic Industry Corporation
1650 Bon Hill Road
Mississauga, Ontario
Canada L5T1C8
- or - 255 Fire Tower Drive
Tonawanda, NY 14150
Attn: Bill Steeley
(905) 795-9274 -or- (905) 399-3697
Parts: (416) 765-9274Page 1
******************************************************************
Gas Detection System
Contact: Basic Systems, Inc.
P.O. Box 767
Cambridge, OH 43725
Doug Law, Project Engineer
(614) 685-2511 ext. 317
Job: Job #113
Service Procedures:
Personnel Responsible: AM Open Person
Each Week: At the Gas Detection Panel in the electrical room, check the reading for each sensor. The “Hold” button on each controller will release the display to scan through the channels. Sensors reading outside of 13% to +3% LFL when no gas is present at the sensors must be calibrated. The procedure for calibrating the gas sensors is in the Det-Tronics instruction manual in Sec. 9 of your Operation and Maintenance manual.
Personnel Responsible: AM Open Person
Each Month: The following devices should be tested for proper operation: Horns, Strobe Lights, Emergency Lights, and Hazardous Exhaust Fans. The manual switches for each of these devices are located on the front of the Gas Detection Panel.
Personnel Responsible: Class I and II Mechanic
Each Week: Calibrate all gas sensors as explained in the Det-Tronics instruction manual in Sec. 9 of your Operation and Maintenance Manual. A test form is shown on Page 32 of the Det-Tronics manual.
Calibration Procedure for Natural Gas Sensors in Garage:
- Unscrew large black cap
- Plug meter into sensor (meter will get its power from the sensor’s circuits)
- Use the “zero” screw (on the sensor) to adjust the reading to “0”
- Snap the line, from the test-gas bottle, to the sensor and then open the valve on the bottle
- Adjust the “span” screw (on the sensor) until the meter reads “50” - Note: The test-gas is at a concentration of 50% of the level needed for explosion
- Push the “sensitivity” button on the meter and hold, the meter should read 15 or more – if it does not, the sensor is bad (the instructions are on the bottom of the meter)
- Close the valve on the bottle and remove test-gas line from the sensor
- Wait until the meter reading is below “10” before removing the test-gas line from the sensor (to avoid triggering the alarm) – Note: The meter will be giving the system monitor a false reading during calibration to avoid triggering the alarm
- Remove meter
- Fill out and place a calibration tag inside the big black cap
- Replace cap – turn on a minimum of five turns, cap only needs to be “hand-snug” Page 2
*******************************************************************
Hoist
Each time the hoist is used:
-Check/feel around the cylinders for nicks and leaks
-Keep the seal area clean
-If nicks are found, use a fine stone to remove
-This should help keep the seals from leaking
Personnel Responsible: All Maintenance Persons
*******************************************************************
Building Emergency Exits/Lights and Lighting Insides/Outside
See High Tech Electronic Book
Each Month:
-Check for lights, use the checklist for exit lights (sample attached)
-Noticfy the Maintenance Supervisor of any others
-CATA’s Maintenance Staff will change light bulbs.
Personnel Responsible: AM Open Person
Outside Pole Lights and any Electrical Problems that CATA Maintenance cannot perform:
Shaffer Electronic Company
24 hours a day for emergency service
(814) 383-2796 (Charlie) and then (814) 383-2621 (Guy Shaffer)
8:00 a.m. – 5:00 p.m. for non-emergency service
(814) 355-7031
******************************************************************
Exhaust Fans See Akin’s Bros. Book, Sec. 10
Contractor: Trane
(800) 451-6335
******************************************************************
Rapid Air Furnace for Maintenance and Storage (located on the roof)
See Akin’s Bros. book, Sec. 6-MUA-2
Each Spring and Fall: Check and adjust belts, grease motors, and fan bearings
Contractor: Trane
(800) 451-6335
Page 3
Manufacturer: Rapid Engineering, Inc.
1100 Seven Mile Road, N.W.
P.O. Box 700
Comstock Park, MI 49321-0700
(616) 784-0500
ICE UNIT HEATER ON UNIMART END OF STORAGE (2000)
MARC-Service Inc.
135 Suite 3
Windber, PA 15963
Attn: Tom Naglic
(814) 467-8611
(814) 467-5858 (Fax)
Note: 10 year full service on fan wheel parts and labor
2 year full service warranty
Trane repairs unit and does PMs
Installed by: Aven Fire Systems, Inc.
10 East Clayton Avenue
New Castle, PA 16102-1893
Annual service by bid
Inspected by: John C. Hazel, Inc.
216 S. Allegheny Street
Bellefonte, PA 16823
(814) 355-4841
*******************************************************************
Oil Water Separator
Yearly: Check for the oil, have it pumped out by waste oil hauler
*******************************************************************
Electrical Repairs
Contact: Shaffer Electric Company
(814) 355-7031
(814) 383-4114 (Fax)
*******************************************************************
York Furnace for Administrative BuildingSee Akin’s Bros. Book, Sec. 1-ACU-1
Spring & Fall: Check and adjust belts, grease motors, and fan bearing and change filters
Outside Contractor Responsible: Trane
(800) 451-6335
Page 4
********************************************************************
Controls for Heating System in Administration Building
Contact: Trane System
(800) 451-6335
*******************************************************************
Generator See High Tech Electric Book, Sec. 3
Each Month: Run generator and record on sheet on generator
Each Friday Morning/Each Month: Turn on water test valve for sprinkler system at exit door in bus storage near front fish pond. Alarm will go off. You must go to the generator room and silence the alarm. Do this early in the morning while the generator is running. Do to the tank room and record the date and sign the sheet.
Each Week: Look at main water valves in the tank room and make sure they are open. Record the date and sign the sheet.
Personnel Responsible: AM Open Person
Repairs: Breon’s Inc.
(814) 359-2947
Model: Onan #DL6TB
Contact: Onan Corporation
1400 73rd Avenue N.E.
Minneapolis, MC 55432
(800) 888-ONAN
********************************************************************
Floor Drains See McCarl’s Book, Sec. 3
Each Spring & Fall: Clean out roof drains
Every 3 Months: Clean out floor drains every three (3) months
Personnel Responsible: Maintenance Person
********************************************************************
Fire Sprinkler System See attached contract
See McCarl’s Book, Sec. 4
Test Once a Year: Simplex
(800) 882-8405
Personnel Responsible: Maintenance Person
********************************************************************
Water Heaters
Each Month: Check underneath monthly for paper or flammable (to be done when checking inside lighting fixtures)
Person Responsible: Maintenance Person
Page 5
Overhead Doors (Steel)
Every September & April:
-Clean with soap and water
-Check for loose sprockets, chains, bolts, nuts, etc., lubricate chains, gear boxes for lubricants
Personnel Responsible for Repairs: Class I or II Mechanic
Repairs: (Old Kenner type C144014)
Parts: North American Door
(216) 828-2291 - or – (216) 674-7015
Attn: Tom Hamilton, Jim Wickline, Paul Kalkre
Local Distributer: Ron Anderson, Everite Door
(800) 233-0248
Flexon Doors
(800) 365-3667
Manuals on bookshelf #2 of bookcase #1
********************************************************************
Ground Maintenance
Personnel Responsible: CATA Maintenance Department
********************************************************************
Evergreen beds, mulching and week control
Personnel Responsible: CATA Maintenance Department
*******************************************************************
Underground Fuel Tanks and Oil Tanks See McCarl’s Book
Sensors and monitoring equipment/installed by:
Stein Equipment Sales, Inc.
4158 Library Road
Pittsburgh, PA 15234
(412) 854-0501
Paper for Printer: GE Sell
Altoona, PA
(814) 695-6171
Service Information: EMCO Wheaton
Leak Sensor and Tank
Monitor II
(800) 342-6125Page 6
*******************************************************************
Roof Flat Over Maintenance Bus Storage
Contact: Marcon Inc. Do a inspection twice a year.
2000 Clyde Avenue
State College, PA 16801
(814) 238-2800
Roof Repairs: (800) 441-3433
**********************************************************
Roof Shingles on Administrative Side
New Roof (12-97): Add MinRick Grissinger, Southern Contactors
(814) 448-9350
********************************************************************
Telephone
Repairs: Morefield Communications
(800) 876-2486
Phone Lines: Verizon
(800) 275-2355
Long Distance: (800) 326-0559
*******************************************************************
Administration Building Cleaning
Contact: Sanitary Maintenance
(814) 359-3222
*******************************************************************
Bus Radios
Service: Centre Communications
(814) 234-2345
*******************************************************************
Time Clocks
Maintenance: Simplex Corporation
(800) 882-8405
*******************************************************************
Fire Alarm System
Maintenance: Simplex Corporation
(800) 882-8405
*******************************************************************
Computers/PC System Centre PC- Net 237 7383
*******************************************************************
Pumping Station (CNG)
Personnel Responsible: All Maintenance Persons
Contact/Service: CATA Maintenance Dept.
******************************************************************
Radio Repairs (All buses and service vehicles)
Service: Centre Communications
(814) 234-2345
*******************************************************************
Snow Removal
Bus Shelters: CATA Maintenance Department
Perimeter Sidewalks: CATA Maintenance Department
*******************************************************************
Plumbing
Contact: PBCI-Allen
(814) 238-3756Page 8