Motor Control Centre – 600 V – Data Sheet(Ref- SPEC-54004)
Plant: / Date: / By:Area: / PO# / Rev:
Project: / Project No:
Manufacturer shall complete and submit the following technical information with bid documents as well as after award of purchase order.
ITEM # / ITEM DESCRIPTION / DESIGN REQUIREMENTS1 / MCC - GENERAL:
1.1 / MCC Manufacturer:
1.2 / MCC Model Number:
1.3 / Quantity:
1.4 / MCC Equipment Number:
1.5 / Design Maximum Ambient Temperature (°C):
1.6 / Design Minimum Ambient Temperature (°C):
1.7 / Design Maximum Relative Humidity (%):
1.8 / Total Weight (kg):
1.9 / Power Cable Entry:
1.10 / -
2 / MCC - ENCLOSURE:
2.1 / Enclosure Type:
2.2 / MCC Construction:
2.3 / MCC Depth (Front Only):
2.4 / MCC Height:
2.5 / MCC Width (Standard Section):
2.6 / Transition Compartment:
2.7 / Vertical Section Material:
2.8 / Vertical Section Features:
2.9 / -
2.10 / -
3 / MCC - ELECTRICAL REQUIREMENTS:
3.1 / Nominal Supply Voltage (V): / 600 V ± 10 %
3.2 / Nominal Supply Frequency (Hz): / 60 Hz ± 5 %
3.3 / Number of Phases: / 3
3.4 / Wire System: / 3 Wire
3.5 / Symmetrical Short Circuit Current:
3.6 / System Grounding:
3.7 / -
3.8 / -
3.9 / -
3.10 / -
ITEM # / ITEM DESCRIPTION / DESIGN REQUIREMENTS
4 / MAIN HORIZONTAL BUS FEATURES:
4.1 / Main Horizontal Bus Material: / Copper
4.2 / Main Horizontal Bus Plating: / Tin
4.3 / Main Horizontal Bus Rating (A):
4.4 / Main Horizontal Bus Fault Bracing (kA):
4.5 / Main Horizontal Bus Features:
4.6 / -
4.7 / -
4.8 / -
4.9 / -
4.10 / -
5 / MAIN VERTICAL BUS FEATURES:
5.1 / Main Vertical Bus Material: / Copper
5.2 / Main Vertical Bus Plating: / Tin
5.3 / Main Vertical Bus Rating (A):
5.4 / Main Vertical Bus Fault Bracing (kA):
5.5 / Additional Features: / Plug-in and Unit Loads
5.6 / Additional Features: / Stab Openings with Automatic Shutters
5.7 / -
5.8 / -
5.9 / -
5.10 / -
6 / HORIZONTAL GROUND BUS FEATURES:
6.1 / Horizontal Ground Bus Material: / Copper
6.2 / Horizontal Ground Bus Plating: / None
6.3 / Horizontal Ground Bus Size: / ¼” x 2”
6.4 / Horizontal Ground Bus Features:
6.5 / -
6.6 / -
6.7 / -
6.8 / -
6.9 / -
6.10 / -
ITEM # / ITEM DESCRIPTION / DESIGN REQUIREMENTS
7 / VERTICAL GROUND BUS FEATURES:
7.1 / Vertical Ground Bus Material: / Copper
7.2 / Vertical Ground Bus Plating: / None
7.3 / Vertical Ground Bus Size:
7.4 / Vertical Ground Bus Features:
7.5 / -
7.6 / -
7.7 / -
7.8 / -
7.9 / -
7.10 / -
8 / MAIN LUG FEATURES:
8.1 / Main Lug Cable Entry:
8.2 / Main Lug Cables per Phase:
8.3 / Main Lug Cable Size:
8.4 / Main Lug Type: / Compression (Vendor Supplied)
8.5 / -
8.6 / -
8.7 / -
8.8 / -
8.9 / -
8.10 / -
9 / MAIN CIRCUIT BREAKER FEATURES:
9.1 / MCB Type: / 600 V ± 10 %
9.2 / MCB Frame: / 60 Hz ± 5 %
9.3 / MCB Trip: / 3
9.4 / MCB Fault Interrupting Capacity: / 3 Wire
9.5 / MCB Options:
9.6 / -
9.7 / -
9.8 / -
9.9 / -
9.10 / -
ITEM # / ITEM DESCRIPTION / DESIGN REQUIREMENTS
10 / MONITORING FEATURES:
10.1 / PT’s for Incoming Metering:
10.2 / CT’s for Incoming Metering:
10.3 / Incoming Metering Type:
10.4 / Power Monitor Communication Module :
10.5 / Power Monitor Communication Protocol:
10.6 / Ground Fault CT's
10.7 / -
10.8 / -
10.9 / -
10.10 / -
11 / STARTER UNIT FEATURES:
11.1 / Starter Unit Types: / FVNR and FVR
11.2 / Starter Unit Disconnecting Means: / Fusible Disconnect Switch
11.3 / Starter Fuses: / Vendor Supplied per single line
11.4 / Starter Unit Fault Interrupting Capacity:
11.5 / Starter Unit Overload Relay:
11.6 / Starter Unit Heater Elements:
11.7 / Starter Unit NO Alarm Contact:
11.8 / Starter FVNR Auxiliary Contacts: / 2 NO and 2 NC
11.9 / Starter FVR Auxiliary Contacts: / 2 NO and 1 NC
11.10 / Minimum Starter Size: / NEMA Size 1
11.11 / Starter Pushbuttons:
11.12 / Starter Selector Switches: / Control Power ON/OFF (≥ Size 4)
11.13 / Starter Pilot Lights (Push-to-Test):
11.14 / Starter Communication Module:
11.15 / Starter Communication Protocol:
11.16 / -
11.17 / -
11.18 / -
11.19 / -
ITEM # / ITEM DESCRIPTION / DESIGN REQUIREMENTS
12 / DISTRIBUTION UNIT FEATURES:
12.1 / Distribution Unit Disconnecting Means: / Fusible Disconnect Switch
12.2 / Distribution Unit Fuses: / HRC Form I Class J (Vendor Supplied)
12.3 / Distribution Unit Fault Interrupting Capacity: / 65 kA
12.4 / Distribution Unit Communication Module:
12.5 / -
12.6 / -
12.7 / -
12.8 / -
12.9 / -
12.10 / -
13 / VFD FEATURES:
13.1 / VFD Unit Disconnecting Means: / Fusible Disconnect Switch
13.2 / VFD Unit Fuses: / HRC Form I Class HSJ (Vendor Supplied)
13.3 / VFD Unit Fault Interrupting Capacity (kA):
13.4 / VFD Additional Information:
13.5 / VFD Unit Communication Module:
13.6 / -
13.7 / -
13.8 / -
13.9 / -
13.10 / -
14 / CONTROL TRANSFORMER FEATURES:
14.1 / Control Transformers: / Individual
14.2 / Control Transformer Voltage (V): / 600/120 V
14.3 / Control Transformer Excess Capacity: / 100 Watts above standard
14.4 / Control Transformer Fusing: / Primary/Secondary (Vendor Supplied)
14.5 / -
14.6 / -
14.7 / -
14.8 / -
14.9 / -
14.10 / -
ITEM # / ITEM DESCRIPTION / DESIGN REQUIREMENTS
15 / PANEL BOARD FEATURES:
15.1 / Panel Board Manufacturer:
15.2 / Panel Board Model Number:
15.3 / Number of Circuits:
15.4 / Panel Board Equipment Number:
15.5 / -
15.6 / -
15.7 / -
16 / MCC - DEVICE QUANTITIES
16.1 / Size 1 FVNR Combination Starter:
16.2 / Size 1 FVR Combination Starter:
16.3 / Size 2 FVNR Combination Starter:
16.4 / Size 2 FVR Combination Starter:
16.5 / Size 3 FVNR Combination Starter:
16.6 / Size 3 FVR Combination Starter:
16.7 / Size 4 FVNR Combination Starter:
16.8 / Size 4 FVR Combination Starter:
16.9 / Size 5 FVNR Combination Starter:
16.10 / Size 5 FVR Combination Starter:
16.11 / Size 6 FVNR Combination Starter:
16.12 / Size 6 FVR Combination Starter:
16.13 / Size 7 FVNR Combination Starter:
16.14 / Size 7 FVR Combination Starter:
16.15 / 30 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.16 / 60 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.17 / 100 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.18 / 200 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.19 / 400 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.20 / 600 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.21 / 800 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.22 / 1000 A, 3-Pole, 600 V Fusible Disconnect Switch:
16.23 / -
16.24 / -
16.25 / -
T-513