/ IECEx Certificate of Conformity
Annexe
Annexe for Certificate No.: / IECEx TSA 12.0018X / Issue No.: / 0

Equipment

The Squirrel Cage Induction Motor Frames 71 to 250 are totally enclosed fan cooled (TEFC) motors with integral cast cooling fins on frame and end shields. They have winding designs which are suitable for use on 200 to 690 Volts, 50 Hz /60 Hz power systems and incorporate windings with double enamelled class ‘F’ or class ‘H’ insulation, which are impregnated with an insulating varnish. The enclosures are made of high grade cast iron with foot and/or C Face/D Flange mounting for horizontal or vertical shaft axis up or down. The external fan is of non-sparking construction and is made of polypropylene, bronze, aluminium or cast iron. They are bi-directional axial flow types, for vertical shaft down mounted option motors are fitted with canopy over fan cover inlet. On the motors up to and including 250, the terminal box is mounted on the right hand side viewed from drive end with option of left hand side. All terminal boxes are sealed with one-piece neoprene gasket between frame, box and gland plate. Variations to sealing arrangements are made to meet the client-specified IP Code requirements such as V-ring, gamma seal or oil seal for bearing sealing arrangement. Motors frame size D160 and larger are fitted with PTC thermistors protection within windings with the leads terminated in the main terminal box.

The Ex tD version of the motors have gaskets glued and additional component machining as per certified drawings. Lifting eyebolt holes are also sealed and alternative grease seals are used at the shaft/bearing areas. These features can also utilise to achieve optional IP56/IP66 ratings on Ex nA and Ex e motors.

Optionally the equipment may be supplied with one or more of the variants:

a)  Auxiliary Terminal Boxes mounted on the sides of the Main Terminal Box to facilitate connection to:

i)  Anti-condensation heaters rated for operation up to 240 volts

ii)  PTC Thermistors

iii)  Resistance Temperature Devices (RTD's)

iv)  Thermocouples

v)  Auxiliary circuits connected via auxiliary terminal block as detailed in certified drawing lists.

b)  Drain plugs of porous material fitted to the NDE and DE end-shields or motor frame, according to the motor mounting position. Provision is also made for fitting plugs to the end-shields at the lowest point when the motor is mounted vertically.

c)  Mechanical attachments for the fitting of bearing condition monitoring devices.

d)  Alternative ball, roller or angular contact bearings to suit the drive application.

e)  Weather cover.

f)  Double shaft extension.

g)  Non-standard shaft dimensions.

h)  The retrofitting of Auxiliaries after the stator has been varnished.

i)  Alternative sealing arrangements to provide for the IP classifications listed in Table 1.

j)  Alternative supply from a variable voltage variable frequency (VVVF) drive with alternative windings suitable for use in conjunction with a (VVVF) drive for Ex nA and Ex tD motors only.

k)  Alternative cable entries as detailed in the certified drawing list with option for blank gland plate.

Table 1: Summary of IP Classifications

Type of Explosion Protection

/ IP Classification / Temp Classification @ Amb
‘Ex e’ / IP55 or IP56 or IP66 / T3 @ 40°C (Tamb.)
‘Ex n’ / IP55 or IP56 or IP66 / T3 @ 55°C (Tamb.)
‘Ex tD’ / IP66 / T4 @ 55°C (Tamb.)

Table 2: Summary of Certified Equipment (2-pole and 4-pole)

2-pole Configuration

/

4-pole Configuration

Frame

/ kW (50Hz)
(Motor Type, refer Note 1) / Voltage / Frame / kW (50Hz) (Motor Type, refer Note 1) / Voltage

71

/ 0.37 /

71

/ 0.37
71 / 0.55 / 80 / 0.55
80 / 0.75 / 80 / 0.75
80 / 1.1 / 90S / 1.1
90S / 1.5 / 90L / 1.5
90L / 2.2 / 100L / 2.2
100L / 3 / 100L / 3
112M / 4 / Up to and / 112M / 4 / Up to and
132S / 5.5 / including / 132S / 5.5 / including
132S / 7.5 / 690 V / 132M / 7.5 / 690 V
160M / 11 / 160M / 11
160M / 15 / 160L / 15
160L / 18.5 / 180M / 18.5
180M / 22 / 180L / 22
200L / 30 / 200L / 30
200L / 37 / 225S / 37
225M
/ 45 / 225M / 45
250S / 55 / 250S / 55
250M / 75 / 250M / 75

Table 3: Summary of Certified Equipment (6-pole and 8-pole)

6-pole Configuration

/ 8-pole Configuration
Frame / kW (50Hz)
(Motor Type, refer Note 1) / Voltage / Frame / kW (50Hz)
(Motor Type, refer Note 1) / Voltage

71

/ 0.18 /

80

/ 0.18
80 / 0.37 / 90S / 0.37
80 / 0.55 / 90L / 0.55
90S / 0.75 / 100L / 0.75
90L / 1.1 / 100L / 1.1
100L / 1.5 / 112M / 1.5
112M / 2.2 / 132S / 2.2
132S / 3 / Up to and / 132M / 3 / Up to and
132M / 4 / including / 160M / 4 / including
132M / 5.5 / 690 V / 160M / 5.5 / 690 V
160M / 7.5 / 160L / 7.5
160L / 11 / 180L / 11
180L / 15 /

200L

/ 15
200L / 18.5 / 225S / 18.5
200L / 22 / 225M / 22
225M / 30 / 250S / 30
250S / 37 / 250M / 37
250M / 45

Notes to Tables 2 and 3:

1)  Motor Types are detailed in Table 4. Where motor type is not listed then kW rating / speed applies to all Motor Types.

2)  For tE times, refer to Motor Type as detailed in Table 4 and tE times calculations as detailed in the relevant drawing for Motor Type from the Certified Drawing Lists.

3)  A suffix letter to frame size maybe added for indication of A = 2 pole, B = 4~8 pole direct drive, C = 4~8 pole direct / belt drive.

4)  The electrical rating of the equipment at 60 Hz can be 1.15 times the value given in Tables 2 and 3.

Table 4: Motor Types / Efficiency Levels

MOTOR TYPE - HORIZONTAL FOOT
HORIZONAL FOOT / FLANGE / MOTOR TYPE VERTICAL FLANGE /
HORIZONTAL FLANGE
Protection / Standard
Efficiency / High
Efficiency / Premium
Efficiency
IE3 / Standard
Efficiency / High
Efficiency / Premium
Efficiency
IE3
IE1 / IE2 / IE1 / IE2
Ex e / AEEBXE / AEHBXE / AEMBXE / AEVBXE / AEUBXE / AEMVXE
Ex nA / AEEBXJ / AEHBXJ / AEMBXJ / AEVBXJ / AEUBXJ / AEMVXJ
Ex tD / AEEBXD / AEHBXD / AEMBXD / AEVBXD / AEUBXD / AEMVXD
FRAME / 71 ~ 250 / 80 ~ 250 / 80 ~ 250 / 71 ~ 250 / 80 ~ 250 / 80 ~ 250

Conditions of Certification:

1.  Where ‘Ex e’ motors are applied as variable speed (VVVF) drives, each motor and its specified controller shall be tested as a combination unit in accordance with IEC60079-0, IEC60079-7, TECO test procedures and the duty cycle for each application to ensure that the limiting temperature and temperature class are not exceeded.

2.  For ‘Ex e’ applications, the electrical protection shall be set in accordance with the tE time for each motor given in the relevant drawing from the Certified Drawing list, depending on motor type as detailed in table 4.

3.  Where ‘Ex nA’ motors are applied as variable speed (VVVF) drives, either each motor shall be type-tested for this duty in association with the specified converter and the protective devices provided or the motor temperature-rise shall be calculated in accordance with IEC60079-0 and IEC 60079-15 for the duty required/specified to ensure that the limiting temperature and temperature class are not exceeded.

4.  Where ‘Ex tD’ motors are applied as variable speed (VVVF) drives each motor shall be fitted with at least three thermistors, one in each phase having a reference temperature so as to ensure that the winding insulation is adequately protected against overheating for the insulation used, and supply is disconnected before its limiting temperature has been exceeded under the worst conditions of operation. The temperature class shall not be exceeded.

5.  Where anti-condensation heaters are fitted, the supply to the heaters shall only be switched on after the main supply to each motor has been disconnected.


Drawings Relating to Issue 0:

Manufacturer’s Documents /
Document / Drawing No.: / Page/s: / Title: / Revision Level: / Date:
(yyyy-mm-dd) /
Motor range 71-250 /
31057B651014 / 1 / Schematic Drawing 3 ~ phase induction foot mounted type motor / 4 / 2012-06-14 /
31057B651024 / 1 / Schematic Drawing 3 ~ phase induction flange mounted type motor / 4 / 2012-06-14 /
31057B651034 / 1 / Schematic Drawing 3 ~ phase induction foot mounted type motor / 4 / 2012-06-14 /
31057B651044 / 1 / Schematic Drawing 3 ~ phase induction vertical type motor / 4 / 2012-06-14 /
31057C446153 / 1 / Threaded Entries for Frames 71~ 180(4P/6P/8P) / 3 / 2008-05-05 /
31057C446172 / 1 / Threaded Entries for Frames 180(2P) ~250 / 2 / 2008-04-29 /
31057B651050 / 1 / Typical Stator & Rotor & Shaft materials / 0 / 2008-04-14 /
31057C446143 / 1 / Name Plate and Label Position (Frames 71-250) / 3 / 2012-08-09 /
31057C446011 / 1 / Air Gap Calculation & relative data for Frames 71-250 / 1 / 2008-05-06 /
31057C446020 / 1 / Clearance Between Fan Cover & Fan (for Frames 71-250) / 0 / 2007-11-14 /
31057C446030 / 1 / Clearance between Bracket/Flange Bracket & Shaft (for Frames 71~ 180, 4P/6P/8P) / 0 / 2007-11-14 /
31057C446091 / 1 / Clearance between Bracket/Flange Bracket & Shaft (for Frames 180, 2P ~250) / 1 / 2011-12-07 /
31049R135652 / 1 / Creepage & Clearance / 2 / 2012-08-13 /
31057C446073 / 1 / Terminal Box (Ex e for Frames 71-112) / 3 / 2012-07-05 /
31057C446083 / 1 / Terminal Box (Ex e for Frame 132) / 3 / 2012-07-05 /
31057C446114 / 1 / Terminal Box (Ex e for Frames 160-250) / 4 / 2012-07-05 /
31057C446261 / 1 / Terminal Box (Ex e for Frames 80-225) / 1 / 2012-07-05 /
31057C446132 / 1 / Schematic drawing Terminal Box (for Frames 200-250) / 2 / 2012-08-06 /
31057C446212 / 1 / Schematic drawing Terminal box (for Bearing RTD Ex e, Ex n & Ex tD for Frames 180-250) / 2 / 2012-08-06 /
31057C446221 / 1 / Schematic drawing terminal box (for winding RTD Ex e, Ex n & Ex tD for Frames 180-250) / 1 / 2012-07-05 /
31049R135431 / 1 / Terminal Box Seat Assy Modification (IP55 for Frame 71) / 1 / 2008-05-06 /
31049R135451 / 1 / Terminal Box Seat Assy Modification (IP55 for Frames 71-112) / 1 / 2008-05-06 /
31049R135471 / 1 / Terminal Box Seat Assy Modification (IP55 for Frames 132-180) / 1 / 2008-05-06 /
31057H799041 / 1 / Terminal Box Seat Assy Modification (IP55 for Frame 200) / 1 / 2008-05-19 /
Manufacturer’s Documents /
Document / Drawing No.: / Page/s: / Title: / Revision Level: / Date:
(yyyy-mm-dd) /
31057H799061 / 1 / Terminal Box Seat Assy Modification (IP55 for Frame 225) / 1 / 2008-05-19 /
31057H799081 / 1 / Terminal Box Seat Assy Modification (IP55 for Frame 250) / 1 / 2008-05-19 /
31049R135442 / 1 / Terminal Box Seat Assy Modification (IP66 for Frame 71) / 2 / 2012-07-05 /
31049R135462 / 1 / Terminal Box Seat Assy Modification (IP66 for Frames 71-112) / 2 / 2012-07-05 /
31049R135482 / 1 / Terminal Box Seat Assy Modification (IP66 for Frames 132-180) / 2 / 2012-07-05 /
31057H799052 / 1 / Terminal Box Seat Assy Modification (IP66 for Frame 200) / 2 / 2012-07-05 /
31057H799072 / 1 / Terminal Box Seat Assy Modification (IP66 for Frame 225) / 2 / 2012-07-05 /
31057H799092 / 1 / Terminal Box Seat Assy Modification (IP66 for Frame 250) / 2 / 2012-07-05 /
31057H799470 / 1 / Terminal Box Seat Assy Modification (for Bearing RTD IP66 Frames 180-250) / 0 / 2008-09-02 /
31049R135612 / 1 / Cable Entries for frames 71-250 / 2 / 2008-03-31 /
31057C446042 / 1 / Schematic drawing Terminal Box Ex n & Ex tD for Frame 71 / 2 / 2012-07-05 /
31057C446122 / 1 / Schematic drawing Terminal Box (Ex n & Ex tD for Frame 71, with auxiliary terminal block) / 2 / 2012-07-05 /
31057C446052 / 1 / Schematic drawing Terminal Box Ex n & Ex tD for Frames 80-112 / 2 / 2012-07-05 /
31057C446062 / 1 / Schematic drawing Terminal Box Ex n & Ex tD for Frame 132 / 2 / 2012-07-05 /
31057C446103 / 1 / Schematic drawing Terminal Box Ex n & Ex tD for Frames 160-250 / 3 / 2012-07-05 /
31057C446251 / 1 / Schematic drawing Terminal Box Ex n & Ex tD for Frames 80-225 / 1 / 2012-07-05 /
219801190 / 1 / Oil Seal / 0 / - /
219802190 / 3 / V-Ring / 1 / 2009-10-16 /
31865D063 / 1 / Oil Seal (SC Type) / 4 / 2009-11-23 /
31865D079 / 1 / Gamma Seal (for IP66) / 1 / 2009-06-19 /

Manufacturer’s Documents

/
Document / Drawing No.: / Page/s: / Title: / Revision Level: / Date:
(yyyy-mm-dd) /
Common drawings/documents /
3B040Z039 / 1 / Bearing RTD / 00 / 2008-08-04 /
S9785 / 1 / Resistance temperature detector Stick type S9785 series / K / 1999-02-22 /
31057R9521 / 1 / IECEx Ex e tE time calculation list / 0 / 2012-06-08 /
31057R9522 / 2 / 3-Phase Low voltage squirrel cage motors hazardous area Ex e IEC design N Continuous duty 200-690 V Electrical parameters / 0 / 2012-06-08 /
31057R9981 / 1 / ANTI-CONDENSATION HEATER INFORMATION / 00 / 2008-05-12 /
31057R9981 / 2 / Increased Safety – Type “e” ANTI-CONDENSATION HEATERS FOR ELECTRIC MOTORS AND GENERATOS / - / 2001-08-13 /
31057R9520 / 1 / TECO Design data – Continuous output under converter ( self cooled Ex n/ Ex e*/ Ex tD TEFC IC411) / 0 / 20012-06-08 /
31049R133493 / 1 / Outline dimensions name plate / 3 / 2012-06-08 /
31049R133503 / 1 / Outline dimensions name plate / 3 / 2012-06-08 /
31049R133513 / 1 / Outline dimensions name plate / 3 / 2012-06-08 /