SECTION 26 27 26

WIRING DEVICES

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2010 - 2014 ARCAT, Inc. - All rights reserved

** NOTE TO SPECIFIER ** Pass & Seymour®; electrical wiring devices and accessories.
This section is based on the products of Pass & Seymour, which is located at:

P. O. Box 4822
Syracuse, NY 13221
Toll Free Tel: 877-295-3472
Email: ;
Web: www.legrand.us/PassAndSeymour
[ Click Here ] for additional information.
Need Help with your project? Pass & Seymour specifications consultants are always there to help. To request expert assistance or have your questions answered click here to contact a Specification consultant for your area: http://www.legrand.us/wiremold/arcat-signup.aspx#.U0fa1F4vvWF
From switches to outlets, wall plates to PlugTail devices, Pass & Seymour offers the most complete line of residential, commercial and industrial wiring devices and accessories. All with innovation and intelligence designed in from the start.
.
See our SpecWizard: Click Here

1 GENERAL

1.1   SECTION INCLUDES

** NOTE TO SPECIFIER ** Delete items below not required for project.

1.1.1   Wiring devices, including the following:

1.1.1.1   Straight blade receptacles.

1.1.1.2   GFCI receptacles.

1.1.1.3   Surge protected receptacles (SPD).

1.1.1.4   Locking receptacles.

1.1.1.5   Locking plugs and connectors.

1.1.1.6   Cord and plug sets.

1.1.1.7   Toggle switches.

1.1.1.8   Illuminated switches.

1.1.1.9   Key-operated switches.

1.1.1.10   Momentary contact switches.

1.1.1.11   Wall-box dimmers.

1.1.1.12   Fan speed controls.

1.1.1.13   Occupancy/vacancy sensors.

1.1.1.14   Communications outlets.

1.1.1.15   Wall plates.

1.1.1.16   Floor service fittings.

1.1.1.17   Finishes.

1.2   RELATED SECTIONS

** NOTE TO SPECIFIER ** Delete section below if not relevant to this project; add others as required.

1.2.1   Section 27 10 00 - Structured Cabling.

1.3   SUBMITTALS

1.3.1   Submit under provisions of Section 01 30 00 - Administrative Requirements.

1.3.2   Product Data: Manufacturer's data sheets on each product to be used, including:

1.3.2.1   Preparation instructions and recommendations.

1.3.2.2   Storage and handling requirements and recommendations.

1.3.2.3   Installation methods.

** NOTE TO SPECIFIER ** Delete selection samples if not required.

1.3.3   Selection Samples: For each device and wall plate specified, two complete sets of color chips representing manufacturer's full range of available colors.

1.3.4   Verification Samples: For each finish product specified, two samples of each device and wall plate, representing actual product, color, and patterns.

1.4   QUALITY ASSURANCE

1.4.1   Product Requirements:

1.4.1.1   Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction (AHJ), and marked for permissible application.

1.4.1.2   Comply with NFPA 70.

** NOTE TO SPECIFIER ** Delete if not required.

1.4.1.3   Compliance with Federal Specifications - identified by the federal specification mark (capital letters "F" and "S" each in a wing on either side of the UL Listing mark):

1.4.1.3.1   Receptacles, GFCI's, plugs and cord connectors: Federal Specification number W-C-596.

1.4.1.3.2   Snap switches: Federal Specification number W-S-896.

** NOTE TO SPECIFIER ** Include a mock-up if the project size and/or quality warrant taking such a precaution. The following is one example of how a mock-up on a large project might be specified. When deciding on the extent of the mock-up, consider all the major different types of work on the project.

1.4.2   Mock-Up: Provide a mock-up for evaluation of preparation techniques and installation workmanship.

1.4.2.1   Finish areas designated by Architect.

1.4.2.2   Do not proceed with remaining work until workmanship is approved by Architect.

1.4.2.3   Rework mock-up as required to produce acceptable work.

1.5   DELIVERY, STORAGE, AND HANDLING

1.5.1   Store products in manufacturer's unopened packaging until ready for installation.

1.5.2   Store and dispose of solvent-based materials, and materials used with solvent-based materials, in accordance with requirements of local authorities having jurisdiction.

1.6   PROJECT CONDITIONS

1.6.1   Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

2 PRODUCTS

2.1   MANUFACTURERS

** NOTE TO SPECIFIER ** Need Help with your project? Pass & Seymour specifications consultants are always there to help. To request expert assistance or have your questions answered click here to contact a Specification consultant for your area:http://www.legrand.us/wiremold/arcat-signup.aspx#.U0fa1F4vvWF

2.1.1   Acceptable Manufacturer: Pass & Seymour, which is located at: P. O. Box 4822 ; Syracuse, NY 13221; Toll Free Tel: 877-295-3472; Email: , ; Web: www.legrand.us/PassAndSeymour .

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

2.1.2   Substitutions: Not permitted.

2.1.3   Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.

** NOTE TO SPECIFIER ** Delete paragraphs for straight blade receptacles not required. Delete Article if not required.

2.2   STRAIGHT BLADE RECEPTACLES

2.2.1   Convenience Receptacles 125 V, 15 and 20 A:

2.2.1.1   Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL 498 and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

** NOTE TO SPECIFIER ** Delete products not required. PT connectors available in several types, refer to manufacturer's catalog.

2.2.1.2   Products: Pass & Seymour, 5251 (15A single).

2.2.1.3   Products: Pass & Seymour, 5262 (15A duplex).

2.2.1.4   Products: Pass & Seymour, 5351 (20A single).

2.2.1.5   Products: Pass & Seymour, 5362 (20A duplex).

2.2.1.6   Products: Pass & Seymour, PT5262 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.1.7   Products: Pass & Seymour, PT5362 (20A duplex - use with PTRA6STR prewired pigtail connector).

** NOTE TO SPECIFIER ** Decorator Style Series Receptacles

2.2.1.8   Products: Pass & Seymour, 26252 (15A duplex - Heavy Duty).

2.2.1.9   Products: Pass & Seymour, PT26252 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.1.10   Products: Pass & Seymour, 26352 (20A duplex - Heavy Duty).

2.2.1.11   Products: Pass & Seymour, PT26352 (20A duplex - use with PTRA6STR prewired pigtail connector).

2.2.1.12   Products: Pass & Seymour, TR26261 (15A single).

2.2.1.13   Products: Pass & Seymour, TR26361 (20A single).

** NOTE TO SPECIFIER ** Decorator Style Series Hallway Light and Single Receptacles

2.2.1.14   Products: Pass & Seymour, PS8HWL (20A duplex).

2.2.2   Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:

2.2.2.1   Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL 498 Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

** NOTE TO SPECIFIER ** Delete products not required. PT connectors available in several types, refer to manufacturer's catalog.

2.2.2.2   Products: Pass & Seymour, 8201 (15A single).

2.2.2.3   Products: Pass & Seymour, 8200H (15A duplex).

2.2.2.4   Products: Pass & Seymour, 8301 (20A single).

2.2.2.5   Products: Pass & Seymour, 8300H (20A duplex).

2.2.2.6   Products: Pass & Seymour, PT8200 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.2.7   Products: Pass & Seymour, PT8300 (20A duplex - use with PTRA6STR prewired pigtail connector).

** NOTE TO SPECIFIER ** Isolated-ground receptacles are available in a variety of configurations and ratings including locking-blade types up to 30 A and 600 V. Revise first paragraph and subparagraphs below to suit Project; indicate different types on Drawings.

2.2.3   Isolated-Ground Duplex Convenience Receptacles, 125 V, 15 and 20 A:

2.2.3.1   Comply with NEMA WD 1, NEMA WD configurations 5-15R and 5-20R, UL 498 and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

** NOTE TO SPECIFIER ** Delete products not required. PT connectors available in several types, refer to manufacturer's catalog.

2.2.3.2   Products: Pass & Seymour, IG5261 (15A single).

2.2.3.3   Products: Pass & Seymour, IG5262 (15A duplex).

2.2.3.4   Products: Pass & Seymour, IG5361 (20A single).

2.2.3.5   Products: Pass & Seymour, IG5362 (20A duplex)

2.2.3.6   Products: Pass & Seymour, PTIG5262 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.3.7   Products: Pass & Seymour, PTIG5362 (20A duplex - use with PTRA6STR prewired pigtail connector).

** NOTE TO SPECIFIER ** Decorator Style Series Isolated-Ground Duplex Convenience Receptacles.

2.2.3.8   Products: Pass & Seymour, IG26262 (15A duplex).

2.2.3.9   Products: Pass & Seymour, IG26362 (20A duplex).

2.2.3.10   Products: Pass & Seymour, PTIG26262 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.3.11   Products: Pass & Seymour, PTIG26362 (20A duplex - use with PTRA6STR prewired pigtail connector).

2.2.3.12   Description: Straight blade; equipment grounding contacts shall be connected only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts. In the case of isolated ground device to be used with prewired pigtail connector: no terminal screws are necessary; plastic barrier shall be present to isolate the grounding terminal from the mounting strap and metal boxes.

2.2.4   Isolated Ground Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:

2.2.4.1   Comply with NEMA WD 1, NEMA WD 6 configuration 5-20R, UL 498 Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

** NOTE TO SPECIFIER ** Delete products not required. PT connectors available in several types, refer to manufacturer's catalog.

2.2.4.2   Products: Pass & Seymour, IG8200 (15A duplex).

2.2.4.3   Products: Pass & Seymour, IG8300 (20A duplex).

2.2.4.4   Products: Pass & Seymour, PTIG8200 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.4.5   Products: Pass & Seymour, PTIG8300 (20A duplex - use with PTRA6STR prewired pigtail connector).

2.2.5   Tamper-Resistant Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:

2.2.5.1   Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL 498 Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

** NOTE TO SPECIFIER ** Delete products not required. PT connectors available in several types, refer to manufacturer's catalog.

2.2.5.2   Products: Pass & Seymour, TR62H (15A duplex).

2.2.5.3   Products: Pass & Seymour, TR63H (20A duplex).

2.2.5.4   Products: Pass & Seymour, PTTR62H (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.5.5   Products: Pass & Seymour, PTTR63H (20A duplex - use with PTRA6STR prewired pigtail connector).

2.2.5.6   Products: Pass & Seymour, PTTR8200 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.5.7   Products: Pass & Seymour, PTTR8300 (20A duplex - use with PTRA6STR prewired pigtail connector).

2.2.5.8   Description: Labeled to comply with NFPA 70, "Health Care Facilities" Article, "Pediatric Locations" Section.

2.2.6   Tamper-Resistant Convenience Receptacles, 125V, 15 and 20 A:

2.2.6.1   Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL498 and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

** NOTE TO SPECIFIER ** Delete products not required. PT connectors available in several types, refer to manufacturer's catalog.

2.2.6.2   Products: Pass & Seymour, TR62 (15A duplex).

2.2.6.3   Products: Pass & Seymour, TR63 (20A duplex).

2.2.6.4   Products: Pass & Seymour, PTTR62 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.6.5   Products: Pass & Seymour, PTTR63 (20A duplex - use with PTRA6STR prewired pigtail connector).

2.2.6.6   Products: Pass & Seymour, TR5251 (15A single).

2.2.6.7   Products: Pass & Seymour, TR5262 (15A duplex).

2.2.6.8   Products: Pass & Seymour, TR5351 (single).

2.2.6.9   Products: Pass & Seymour, TR5362 (20A duplex).

2.2.6.10   Products: Pass & Seymour, PTTR5262 (15A duplex - use with PTRA6STR prewired pigtail connector).

2.2.6.11   Products: Pass & Seymour, PTTR5362 (20A duplex - use with PTRA6STR prewired pigtail connector).

** NOTE TO SPECIFIER ** Decorator Style Series Tamper Resistant Receptacles

2.2.6.12   Products: Pass & Seymour, TR26262 (15A duplex).

2.2.6.13   Products: Pass & Seymour, TR26362 (20A duplex).

2.2.6.14   Products: Pass & Seymour, PTTR26262 (15A duplex). - use with PTRA6STR prewired pigtail connector).

2.2.6.15   Products: Pass & Seymour, PTTR26362 (20A duplex). - use with PTRA6STR prewired pigtail connector).

2.2.7   Tamper-Resistant Isolated-Ground, Duplex Convenience Receptacles, 125 V, 15 and 20 A:

2.2.7.1   Comply with NEMA WD 1, NEMA WD configurations 5-15R and 5-20R, UL 498 and Federal Specification W-C-596.

** NOTE TO SPECIFIER ** Delete products not required.

2.2.7.2   Products: Pass & Seymour, TRIG5262 (15A duplex).

2.2.7.3   Products: Pass & Seymour, TRIG5362 (20A duplex).

NOTE TO SPECIFIER ** Decorator Style Series Receptacles

2.2.7.4   Products: Pass & Seymour, TRIG26262 (15A duplex).

2.2.7.5   Products: Pass & Seymour, TRIG26362 (20A duplex).

2.2.7.6   Description: Straight blade; equipment grounding contacts shall be connected only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts.

2.2.8   Tamper-Resistant Isolated-Ground Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:

2.2.8.1   Comply with NEMA WD 1, NEMA WD configurations 5-15R and 5-20R, UL 498 Supplement SD and Federal Specification W-C-596.

** NOTE TO SPECIFIER ** Delete products not required.