SANDWELL M.B.C.
ASBESTOS SURVEY SUMMARY TABLE
Site Name: HIGHFIELDSPRIMARY SCHOOLBEECHES ROAD ROWLEY REGIS B65 ODA
Information Based Upon: BRADLEY SURVEYRef: S12195Date: 22.04.10.
(PLEASE NOTE THIS REPORT IS TO BE READ IN CONJUNCTION WITH SURVEY S12195)
Sample No. /Item No.
/Room No.
/Location
/Item
/Material
/Priority
/Action
/Status
270/420 / 001 / 59 / Basement boilerhouse / Insulation debris to wall(s) / No asbestos detected / N/A / N/A / N/A270/421 / 002 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Amosite Chrysotile / 1 / Programme removal
270/422 / 003 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Amosite Chrysotile / 1 / Programme removal
270/423 / 004 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Amosite Chrysotile / 1 / Programme removal
270/424 / 005 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Chrysotile / 1 / Programme removal
270/425 / 006 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Amosite / 1 / Programme removal
Sample No. /
Item No.
/Room No.
/Location
/Item
/Material
/Priority
/Action
/Status
270/426 / 007 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Amosite Chrysotile / 1 / Programme removal270/427 / 008 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Chrysotile / 1 / Programme removal
270/429 / 009 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Amosite Chrysotile / 1 / Programme removal
270/428 / 010 / 59 / Basement boilerhouse / Asbestos insulation debris to wall(s) / Chrysotile / 1 / Programme removal
270/430 / 011 / 59 / Basement boilerhouse / Insulation debris to ledge / No asbestos detected / N/A / N/A / N/A
270/431 / 012 / 59 / Basement boilerhouse / Asbestos insulation debris to ledge / Amosite / 1 / Programme removal
Sample No. /
Item No.
/Room No.
/Location
/Item
/Material
/Priority
/Action
/Status
270/432 / 013 / 59 / Basement boilerhouse / Asbestos insulation debris to floor / Amosite / 1 / Programme removal270/433 / 014 / 59 / Basement boilerhouse / Asbestos insulation debris to floor / Amosite / 1 / Programme removal
270/434 / 015 / 59 / Basement boilerhouse / Asbestos insulation debris to floor / Amosite / 1 / Programme removal
270/435 / 016 / 59 / Basement boilerhouse / Asbestos insulation debris to floor / Amosite / 1 / Programme removal
270/436 / 017 / 59 / Basement boilerhouse / Asbestos insulation debris to floor / Amosite / 1 / Programme removal
270/437 / 018 / 59 / Basement boilerhouse / Asbestos insulation debris to floor / Amosite / 1 / Programme removal
Sample No. /
Item No.
/Room No.
/Location
/Item
/Material
/Priority
/Action
/Status
270/438 / 019 / 59 / Basement boilerhouse / Insulation debris to pipework / No asbestos detected / N/A / N/A / N/A270/439 / 020 / 59 / Basement boilerhouse / Insulation debris to pipework / No asbestos detected / N/A / N/A / N/A
270/440 / 021 / 59 / Basement boilerhouse / Asbestos insulation debris to pipework joint / Amosite Chrysotile / 1 / Programme removal
270/441 / 022 / 59 / Basement boilerhouse / Asbestos insulation debris to pipework / Amosite Chrysotile / 1 / Programme removal
270/442 / 023 / 59 / Basement boilerhouse / Insulation debris to pipework / No asbestos detected / N/A / N/A / N/A
270/443 / 024 / 59A / Basement boilerhouse oil tank room / Asbestos insulation debris to pipe / Amosite Chrysotile / 1 / Programme removal
Sample No. /
Item No.
/Room No.
/Location
/Item
/Material
/Priority
/Action
/Status
270/444 / 025 / 59A / Basement boilerhouse oil tank room / Insulation debris to oil tank room / No asbestos detected / N/A / N/A / N/A270/445 / 026 / 59A / Basement boilerhouse oil tank room / Insulation debris to wall(s) / No asbestos detected / N/A / N/A / N/A
270/446 / 027 / 59A / Basement boilerhouse oil tank room / Insulation debris to ledge / No asbestos detected / N/A / N/A / N/A
270/447 / 028 / 59A / Basement boilerhouse oil tank room / Insulation debris to wall(s) / No asbestos detected / N/A / N/A / N/A
270/448 / 029 / 59 / Basement boilerhouse / Compressed asbestos fibre gasket(s) / Chrysotile / 1 / Programme removal
No sample, presumed / 030 / 59 / Basement boilerhouse / Asbestos textile fuse tapes / Presumed Chrysotile / 1 / Programme removal
Sample No. /
Item No.
/Room No.
/Location
/Item
/Material
/Priority
/Action
/Status
270/449 / 031 / 59 / Basement boilerhouse / Insulating board panel(s) to wall / No asbestos detected / N/A / N/A / N/A270/450 / 032 / 59 / Basement boilerhouse / Insulating board panel(s) to wall / No asbestos detected / N/A / N/A / N/A
270/451 / 033 / 59 / Basement boilerhouse / Insulation debris to fire alarm / No asbestos detected / N/A / N/A / N/A
H:\Asbestos\Asbestos Survey Information\Highfields Primary School\Highfields Primary School - Asbestos Survey Report Summaries\S12195 Highfield Primary School.doc
Page 1 of 6