GUIDESPECIFICATIONS-50TCQ*07-14

Noteaboutthisspecification:

Carriercreatedthisspecificationin“Masterformat”aspublishedbytheConstructionSpecificationInstitute.Pleasefeel freetocopythisspecificationdirectlyintoyourbuildingspecifications.

RooftopPackagedHeatPump

HVACGuideSpecifications

SizeRange:6to12.5NominalTons

SectionDescription

230680SchedulesforDecentralized HVACEquipment

230680.13DecentralizedUnitaryHVACEquipmentSchedule

230680.13.A.Rooftopunitschedule

1.Scheduleispertheprojectspecificationrequirements.

230716HVACEquipmentInsulation

230716.13Decentralized,RooftopUnits:

230716.13.A.Evaporatorfancompartment:

1.Interiorcabinetsurfacesshallbeinsulatedwithaminimum1/2-in.thick,minimum11/2lbdensity,flexible fiberglassinsulationbondedwithaphenolicbinder,neoprenecoatedontheairside.

2.InsulationandadhesiveshallmeetNFPA90Arequirementsforflamespreadandsmokegeneration.

3.Unitinternalinsulationliningsaremanufacturedtomeetindustryrequirementsformicrobialresistanceasrequiredas partofUL-181andASTMC1071-12,havingbeenevaluatedinaccordancewiththe“MoldGrowthandHumidity” testinUL181,andtestsforfungiresistanceinASTMC1338andASTMG21.Airstreamsurfacesshallbeevaluated inaccordancewiththe“ErosionTest”inUL181,aspartofASTMC1071.

230716.13.B.Electricheatcompartment:

1.Aluminumfoil-facedfiberglassinsulationshallbeused.

2.InsulationandadhesiveshallmeetNFPA90Arequirementsforflamespreadandsmokegeneration.

230913InstrumentationandControlDevicesforHVAC

230913.23SensorsandTransmitters

230913.23.A.Thermostats

1.Thermostatmust:

a.havecapabilitytoenergize2differentstagesofcooling,and2differentstagesofheating.

b.includecapabilityforoccupancyscheduling.

230923Direct-digitalControlsystemforHVAC

230923.13Decentralized,RooftopUnits:

230923.13.A.PremierLink™controller

1.ShallbeASHRAE62compliant.

2.Shallaccept18-32VACinputpower.

3.Shallhaveanoperatingtemperaturerangefrom-40°F(-40°C)to158°F(70°C),10%-95%RH (non-condensing).

4.Shallincludeanintegratedeconomizercontrollertosupportaneconomizerwith4to20mAactuatorinputand nomicroprocessorcontroller.

5.Controllershallacceptthefollowinginputs:spacetemperature,setpointadjustment,outdoorairtemperature, indoorairquality,outdoorairquality,indoorrelativehumidity,compressorlock-out,fireshutdown,enthalpy,fan status,remotetimeclock/doorswitch.

6.ShallacceptaCO2sensorintheconditionedspace,andbedemandcontrolledventilation(DCV)ready.

7.Shallprovidethefollowingoutputs:Economizer,fan,coolingstage1,coolingstage2,heatstage1,heatstage2, heatstage3/exhaust/reversingvalve/dehumidify/occupied.

8.Unitshallprovidesurgeprotectionforthecontrollerthroughacircuitbreaker.

9.ShallbeInternetcapable,andcommunicateataBaudrateof38.4Korfaster.

10.ShallhaveanLEDdisplayindependentlyshowingthestatusofactivityonthecommunicationbus,andprocessor operation.

11.ShallincludeanEIA-485protocolcommunicationport,anaccessportforconnectionofeitheracomputerora Carriertechniciantool,anEIA-485portfornetworkcommunicationtointelligentspacesensorsanddisplays, andaporttoconnectanoptionalLonWorks*plug-incommunicationscard.

12.Shallhavebuilt-inCarrierComfortNetwork®(CCN)protocol,andbecompatiblewithotherCCNdevices, includingComfortLinkandComfortVIEW™controllers.

13.Shallhavebuilt-insupportforCarriertechniciantool.

14.Softwareupgradeswillbeaccomplishedbylocaldownload.Softwareupgradesthroughchipreplacementsare notallowed.

15.Shallbeshockresistantinallplanesto5Gpeak,11msduringoperation,and100Gpeak,11msduringstorage.

16.Shallbevibrationresistantinallplanesto1.5G@20-300Hz.

17.Shallsupportabuslengthof4000ftmax(1219m),60devicesper1000ft(305m)section,and1RS-485 repeaterper1000ftsections.

230923.13.B.RTUOpenMulti-protocol,directdigitalcontroller:

1.ShallbeASHRAE62compliant.

2.Shallaccept18-30VAC,50-60Hz,andconsumer15VAorlesspower.

3.Shallhaveanoperatingtemperaturerangefrom-40°F(-40°C)to130°F(54°C),10%-90%RH (non-condensing).

4.Shallincludebuilt-inprotocolforBACnet†(MS/TPandPTPmodes),Modbus**(RTUandASCII),JohnsonN2 andLonWorks.LonWorksEchelonprocessorrequiredforallLonapplicationsshallbecontainedinseparate communicationboard.

5.Shallallowaccessofupto62networkvariables(SNVT).Shallbecompatiblewithallopencontrollers.

6.BaudrateControllershallbeselectableusingadipswitch.

7.ShallhaveanLEDdisplayindependentlyshowingthestatusofserialcommunication,running,errors,power,all digitaloutputs,andallanaloginputs.

8.Shallacceptthefollowinginputs:spacetemperature,setpointadjustment,outdoorairtemperature,indoorair quality,outdoorairquality,compressorlock-out,fireshutdown,enthalpyswitch,andfanstatus/filterstatus/ humidity/remoteoccupancy.

9.Shallprovidethefollowingoutputs:economizer,fan,coolingstage1,coolingstage2,heatstage1,heatstage2, heatstage3/exhaust/reversingvalve.

10.Shallhavebuilt-insurgeprotectioncircuitrythroughsolidstatepolyswitches.Polyswitchesshallbeusedon incomingpowerandnetworkconnections.Polyswitcheswillreturntonormalwhenthe“trip”conditionclears.

11.Shallhaveabatteryback-upcapableofaminimumof10,000hoursofdataandtimeclockretentionduring poweroutages.

12.Shallhavebuilt-insupportforCarriertechniciantool.

13.ShallincludeanEIA-485protocolcommunicationport,anaccessportforconnectionofeitheracomputerora Carriertechniciantool,anEIA-485portfornetworkcommunicationtointelligentspacesensorsanddisplays, andaporttoconnectanoptionalLonWorkscommunicationscard.

14.Softwareupgradeswillbeaccomplishedbyeitherlocalorremotedownload.Nosoftwareupgradesthroughchip replacementsareallowed.

230933ElectricandElectronicControlSystemforHVAC

230933.13Decentralized,RooftopUnits:

230933.13.A.General:

1.Shallbecompletewithself-containedlowvoltagecontrolcircuitprotectedbyaresettablecircuitbreakeronthe 24-vtransformerside.Transformershallhave75VAcapability.

2.Shallutilizecolor-codedwiring.

3.Shallincludeacentralcontrolterminalboardtoconvenientlyandsafelyprovideconnectionpointsforvital controlfunctionssuchas:smokedetectors,phasemonitor,economizer,thermostat,DDCcontroloptions,lossof charge,freezeswitch,highpressureswitches.

4.Unitshallincludeaminimumofone8-pinscrewterminalconnectionboardforconnectionofcontrolwiring.

5.Shallincludeintegrateddefrostsystemtopreventexcessivefrostaccumulationduringheatingduty,andshallbe controlledasfollows:

a.Defrostshallbeinitiatedonthebasisoftimeandcoiltemperature.

b.A30,60,90,120minutetimershallactivatethedefrostcycleonlyifthecoiltemperatureislowenoughto indicateaheavyfrostcondition.

*LonWorksisa registered trademarkof EchelonCorporation.

†BACnetisaregisteredtrademarkofASHRAE(AmericanSocietyofHeating,RefrigeratingandAir---ConditioningEngineers).

**Modbusis aregisteredtrademarkofSchneiderElectric.

c.Defrostcycleshallterminatewhendefrostthermostatissatisfiedandshallhaveapositiveterminationtimeof 10minutes.

6.Defrostsystemshallalsoinclude:

a.DefrostCycleIndicatorLED.

b.Dipswitchselectabledefrosttimebetween30,60,90and120minutes.Factorysetat30minutes.

c.Moldedplugconnectiontoinsureproperconnection. 230933.23.B.Safeties:

1.Compressorovertemperature,overcurrent.

2.Lossofchargeswitch.

a.Unitswith2compressorsshallhavedifferentsizedconnectorsforthecircuit1andcircuit2lowandhighpressure switches.Theyshallphysicallypreventthecross-wiringofthesafetyswitchesbetweencircuits1and2.

b.Lossofchargeswitchshallusedifferentcolorwirethanthehighpressureswitch.Thepurposeistoassist theinstallerandservicetechniciantocorrectlywireandortroubleshoottherooftopunit.

3.High-pressureswitch.

a.Unitswith2compressorsshallhavedifferentsizedconnectorsforthecircuit1andcircuit2lowandhighpres- sureswitches.Theyshallphysicallypreventthecross-wiringofthesafetyswitchesbetweencircuits1and2.

b.Highpressureswitchshallusedifferentcolorwirethanthelowpressureswitch.Thepurposeistoassistthe installerandservicetechniciantocorrectlywireand/ortroubleshoottherooftopunit.

4.Freezeprotectionthermostat,evaporatorcoil.

5.Automaticreset,motorthermaloverloadprotector.

230993SequenceofOperationsforHVACControls

230993.13Decentralized,RooftopUnits:

230993.13.AINSERTSEQUENCEOFOPERATION

234013PanelAirFilters

234013.13Decentralized,RooftopUnits:

234013.13.A.Standardfiltersection

1.Shallconsistoffactory-installed,lowvelocity,throwaway2-in.thickfiberglassfiltersofcommerciallyavailable sizes.

2.Unitshalluseonlyonefiltersize.Multiplesizesarenotacceptable.

3.Filtersshallbeaccessiblethroughanaccesspanelwith“no-tool”removalasdescribedintheunitcabinetsection ofthisspecification(238119.13.G).

238119Self-ContainedAirConditioners

238119.13Small-CapacitySelf-ContainedAirConditioners(50TCQ*07-14)

238119.13.A.General

1.Outdoor,rooftopmounted,electricallycontrolled,heatingandcoolingunitutilizinga(n)hermeticscrollcom- pressor(s)forcoolingdutyandheatpumpforheatingduty.

2.Factoryassembled,singlepieceheatingandcoolingrooftopunit.Containedwithintheunitenclosureshallbeall factorywiring,piping,controls,andspecialfeaturesrequiredpriortofieldstart-up.

3.UnitshallusePuron®refrigerant.

4.Unitshallbeinstalledinaccordancewiththemanufacturer’sinstructions.

5.Unitmustbeselectedandinstalledincompliancewithlocal,state,andfederalcodes. 238119.13.B.QualityAssurance

1.UnitmeetsASHRAE90.1-2016andIECC-2015minimumefficiencyrequirements.

2.UnitshallberatedinaccordancewithAHRIStandards340/360.

3.UnitshallbedesignedtoconformtoASHRAE15.

4.UnitshallbeETL-testedandcertifiedinaccordancewithANSIZ21.47StandardsandETL-listedandcertified underCanadianstandardsasatotalpackageforsafetyrequirements.

5.InsulationandadhesiveshallmeetNFPA90Arequirementsforflamespreadandsmokegeneration.

6.Unitinternalinsulationliningsshallberesistanttomoldgrowthinaccordancewith“moldgrowthandhumidity” testinASTMC1338,G21,andUL181orcomparabletestmethod.Airstreamsurfacesshallbeevaluatedin accordancewiththe“ErosionTest”inUL181,aspartofASTMC1071.

7.Unitcasingshallbecapableofwithstanding500-hoursaltsprayexposureperASTMB117(scribedspecimen).

8.RoofcurbshallbedesignedtoconformtoNRCAStandards.

9.Unitshallbesubjectedtoacompletelyautomatedruntestontheassemblyline.Thedataforeachunitwillbe storedatthefactory,andmustbeavailableuponrequest.

10.UnitshallbedesignedinaccordancewithULStandard1995,ETLlistedincludingtestedtowithstandrain.

11.Unitshallbeconstructedtopreventintrusionofsnowandtestedtopreventsnowintrusionintothecontrolbox upto40mph.

12.Unitshaketestedtoassurancelevel1,ASTMD4169toensureshippingreliability.

13.HighEfficiencyMotorslistedshallmeetsection313oftheEnergyIndependenceandSecurityActof2007 (EISA2007).

238119.13.C.Delivery,Storage,andHandling

1.Unitshallbestoredandhandledpermanufacturer’srecommendations.

2.Liftedbycranerequireseithershippingtoppanelorspreaderbars.

3.Unitshallonlybestoredorpositionedintheuprightposition. 238119.13.D.ProjectConditions

1.Asspecifiedinthecontract.

238119.13.E.OperatingCharacteristics

1.Unitshallbecapableofstartingandrunningat115°F(46°C)ambientoutdoortemperature,meetingmaximum loadcriteriaofAHRIStandard340/360at10%voltage.

2.Compressorwithstandardcontrolsshallbecapableofoperationfrom25°F(-4°C),ambientoutdoortemperatures.Accessorywinterstartkitis necessary ifmechanically coolingatambienttemperatures below25°F (-4°C).

3.Unitshallbecapableofsimultaneousheatingdutyanddefrostcycleoperationwhenusingaccessoryelectric heaters.

4.Unitshalldischargesupplyairverticallyorhorizontallyasshownoncontractdrawings.

5.Unitshallbefactoryconfiguredforverticalsupplyandreturnconfigurations.

6.Unitshallbefieldconvertiblefromverticaltohorizontalconfiguration.

7.Unitshallbecapableofmixedoperation:verticalsupplywithhorizontalreturnorhorizontalsupplywithvertical return.

238119.13.F.ElectricalRequirements

1.Mainpowersupplyvoltage,phase,andfrequencymustmatchthoserequiredbythemanufacturer. 238119.13.G.UnitCabinet

1.Unitcabinetshallbeconstructedofgalvanizedsteel,andshallbebonderizedandcoatedwithapre-painted

bakedenamelfinishonallexternallyexposedsurfaces.

2.Unitcabinetexteriorpaintshallbe:filmthickness,(dry)0.003inchesminimum,gloss(perASTMD523,60°F /16°C):60,Hardness:H-2HPencilhardness.

3.EvaporatorfancompartmentinteriorcabinetinsulationshallconformtoAHRIStandards340/360minimum exteriorsweatcriteria.Interiorsurfacesshallbeinsulatedwithaminimum1/2-in.thick,1lbdensity,flexible fiberglassinsulation,neoprenecoatedontheairside.Aluminumfoil-facedfiberglassinsulationshallbeusedin theheatcompartment.

4.Unitinternalinsulationliningsshallberesistanttomoldgrowthinaccordancewith“moldgrowthandhumidity” testinASTMC1338,G21,andUL181orcomparabletestmethod.Airstreamsurfacesshallbeevaluatedin accordancewiththe“ErosionTest”inUL181,aspartofASTMC1071.

5.Baseofunitshallhaveaminimumofthreelocationsforthru-the-baseelectricalconnections(factory-installed orfield-installed),standard.

6.BaseRail

a.Unitshallhavebaserailsonaminimumof2sides.

b.Holesshallbeprovidedinthebaserailsforriggingshacklestofacilitatemaneuveringandoverhead rigging.

c.Holesshallbeprovidedinthebaserailformovingtherooftopbyforktruck.

d.Baserailshallbeaminimumof16gaugethickness.

7.Condensatepanandconnections:

a.Shallbeaslopedcondensatedrainpanmadeofanon-corrosivematerial.

b.ShallcomplywithASHRAEStandard62.

c.Shallusea3/4-in.-14NPTdrainconnection,possibleeitherthroughthebottomorendofthedrainpan.

Connectionshallbemadepermanufacturer’srecommendations.

8.Toppanel:

a.Shallbeasinglepiecetoppanelon07thru09sizes,twopieceson12and14sizes.

9.ElectricalConnections

a.Allunitpowerwiringshallenterunitcabinetatasingle,factoryprepared,knockoutlocation.

b.Thru-the-basecapability.

(1.)Standardunitshallhaveathru-the-baseelectricallocation(s)usingaraised,embossedportionofthe unitbasepan.

(2.)Optional,factory-approved,water-tightconnectionmethodmustbeusedforthru-the-baseelectrical connections.

(3.)Nobasepanpenetration,otherthanthoseauthorizedbythemanufacturer,ispermitted.

10.Componentaccesspanels(standard)

a.Cabinetpanelsshallbeeasilyremovableforservicing.

b.Unitshallhaveonefactory-installed,tool-less,removable,filteraccesspanel.

c.Panelscoveringcontrolbox,indoorfan,indoorfanmotor,gascomponents(whereapplicable),andcompressorsshallhavemoldedcompositehandles.

d.HandlesshallbeUVmodified,composite,permanentlyattached,andrecessedintothepanel.

e.Screwsontheverticalportionofallremovableaccesspanelshallengageintoheatresistant,moldedcompositecollars.

f.Collarsshallberemovableandeasilyreplaceableusingmanufacturerrecommendedparts. 238119.13.H.Coils

1.StandardAluminum/CopperCoils:

a.Standardevaporatorandcondensercoilsshallhavealuminumlancedplatefinsmechanicallybondedto seamlessinternallygroovedcoppertubeswithalljointsbrazed.

b.Evaporatorcoilsshallbeleaktestedto150psig,pressuretestedto450psig,andqualifiedtoUL1995burst testat1775psig.

c.Condensercoilsshallbeleaktestedto150psig,pressuretestedto650psig,andqualifiedtoUL1995burst testat1980psig.

2.OptionalPre-coatedaluminumfincondensercoils:

a.Shallhaveadurableepoxy-phenoliccoatingtoprovideprotectioninmildlycorrosivecoastalenvironments.

b.Coatingshallbeappliedtothealuminumfinstockpriortothefinstampingprocesstocreateaninertbarrierbetweenthealuminumfinandcoppertube.

c.Epoxy-phenolicbarriershallminimizegalvanicactionbetweendissimilarmetals.

d.Corrosiondurabilityoffinstockshallbeconfirmedthroughtestingtobenolessthan1000hourssaltspray perASTMB117-90.

e.Corrosiondurabilityoffinstockshallbeconfirmedthroughtestingtohavenovisiblecorrosionafter48 hourimmersioninaroomtemperaturesolutionof5%salt,1%aceticacid.

f.Finstockcoatingshallpass2000hoursofthefollowing:oneweekexposureintheprohesionchamber followedbyoneweekofacceleratedultravioletlighttesting.Prohesionchamber:thesolutionshallcontain 3.5%sodiumchlorideand0.35%ammoniumsulfate.Theexposurecycleisonehourofsaltfogapplication atambientfollowedbyonehourdryingat95F(35C).

3.OptionalCopper-finevaporatorandcondensercoilsonallmodels:

a.Shallbeconstructedofcopperfinsmechanicallybondedtocoppertubesandcoppertubesheets.

b.Galvanizedsteeltubesheetsshallnotbeacceptable.

c.Apolymerstripshallpreventcoilassemblyfromcontactingthesheetmetalcoilpantominimizepotential forgalvaniccorrosionbetweencoilandpan.

4.OptionalE-coatedaluminum-finevaporatorandcondensercoilsonallmodels:

a.Shallhaveaflexibleepoxypolymercoatinguniformlyappliedtoallcoilsurfaceareaswithoutmaterial bridgingbetweenfins.

b.Coatingprocessshallensurecompletecoilencapsulationoftubes,finsandheaders.

c.ColorshallbehighglossblackwithglossperASTMD523-89.

d.Uniformdryfilmthicknessfrom0.8to1.2milonallsurfaceareasincludingfinedges.

e.Superiorhardnesscharacteristicsof2HperASTMD3363-92Aandcross-hatchadhesionof4B-5Bper ASTMD3359-93.

f.Impactresistanceshallbeupto160in.-lb(ASTMD2794-93).

g.Humidityandwaterimmersionresistanceshallbeuptominimum1000and250hoursrespectively(ASTM D2247-92andASTMD870-92).

h.Corrosiondurabilityshallbeconfirmedthroughtestingtobenolessthan6000hourssaltsprayperASTM B117-90.

238119.13.I.RefrigerantComponents

1.Refrigerantcircuitshallincludethefollowingcontrol,safety,andmaintenancefeatures:

a.Fixedorificemeteringsystemshallpreventmal-distributionoftwo-phaserefrigerantbyincludingmultiple fixedorificedevicesineachrefrigerationcircuit.Eachorificeistobeoptimizedtothecoilcircuititserves.

b.Refrigerantfilterdrier.

c.Servicegaugeconnectionsonsuctionanddischargelines.

d.Pressuregaugeaccessthroughaspeciallydesignedaccessportinthetoppaneloftheunit.

e.Suctionlineaccumulatortoprovideprotectioninalloperatingmodesfromcooling,heatingandreverse cycleswitching.

2.Thereshallbegaugelineaccessportinthetopoftherooftop,coveredbyablack,removableplug.

a.Theplugshallbeeasytoremoveandreplace.

b.Whentheplugisremoved,thegaugeaccessportshallenablemaintenancepersonneltoroutetheirpressure gaugelines.

c.Thisgaugeaccessportshallfacilitatecorrectandaccuratecondenserpressurereadingsbyenablingthe readingwiththecompressoraccesspanelon.

d.Theplugshallbemadeofaleakproof,UV-resistant,compositematerial.

3.Compressors

a.Unitshalluseonefullyhermetic,scrollcompressorforeachindependentrefrigerationcircuit.

b.Modelsshallbeavailablewithsinglecompressordesignson07models,plusadditional2compressor (stage)modelsfrom08-14sizes.

c.Compressormotorsshallbecooledbyrefrigerantgaspassingthroughmotorwindings.

d.Compressorsshallbeinternallyprotectedfromhighdischargetemperatureconditions.

e.Compressorsshallbeprotectedfromanovertemperatureandover-amperageconditionsbyaninternal,mo- toroverloaddevice.

f.Compressorshallbefactorymountedonrubbergrommets.

g.Compressormotorsshallhaveinternallinebreakthermal,currentoverloadandhighpressuredifferential protection.

h.Crankcaseheatersshallbeutilizedonallmodelstoprotectcompressorwithspecificrefrigerantcharge. 238119.13.J. FilterSection

1.Filtersaccessisspecifiedintheunitcabinetsectionofthisspecification.

2.Filtersshallbeheldinplacebyapivotingfiltertray,facilitatingeasyremovalandinstallation.

3.Shallconsistoffactory-installed,lowvelocity,throw-away2-in.thickfiberglassfilters.

4.Filtersshallbestandard,commerciallyavailablesizes.

5.Onlyonesizefilterperunitisallowed. 238119.13.K.EvaporatorFanandMotor

1.Evaporatorfanmotor:

a.Shallhavepermanentlylubricatedbearings.

b.Shallhaveinherentautomatic-resetthermaloverloadprotectionorcircuitbreaker.

c.Shallhaveamaximumcontinuousbhpratingforcontinuousdutyoperation;nosafetyfactorsabovethat ratingshallberequired.

2.Belt-drivenEvaporatorFan:

a.Beltdriveshallincludeanadjustablepitchmotorpulley.

b.Shallusesealed,permanentlylubricatedball-bearingtype.

c.Blowerfanshallbedoubleinlettypewithforward-curvedblades.

d.Shallbeconstructedfromsteelwithafinishthataidswithcorrosionresistanceanddynamicallybalanced. 238119.13.L. CondenserFansandMotors

1.Condenserfanmotors:

a.Shallbeatotallyenclosedmotor.

b.Shallusepermanentlylubricatedbearings.

c.Shallhaveinherentthermaloverloadprotectionwithanautomaticresetfeature.

d.Shalluseashaftdowndesignonallmodels.

2.CondenserFans:

a.Shallbeadirectdrivenpropellertypefan.

b.Shallhavealuminumbladesrivetedtosteelspidersthathavecorrosionresistantpropertiesandshallbe dynamicallybalanced.

238119.13.M.SpecialFeatures,OptionsandAccessories

1.Staged AirVolumeSystem(SAVt)forallmodels.

a.Evaporatorfanmotor:

(1.)Shallhavepermanentlylubricatedbearings.

(2.)Shallhaveamaximumcontinuousbhpratingforcontinuousdutyoperation;nosafetyfactorsabove thatrating.

(3.)ShallbeVariableFrequencydutyand2-speedcontrol.

(4.)Shallcontainmotorshaftgroundingringtopreventelectricalbearingflutingdamagebysafelydivertingharmfulshaftvoltagesandbearingcurrentstoground.

2.VariableFrequencyDrive(VFD).Onlyavailableon2-speedindoorfanmotoroption(SAV):

a.Factory-suppliedVFDsqualify,throughABB,fora12-monthwarrantyfromdateofcommissioningor18 monthsfromdateofsale,whicheveroccursfirst.

b.Shallbeinstalledinsidetheunitcabinet,mounted,wiredandtested.

c.ShallcontainElectromagneticInterference(EMI)frequencyprotection.

d.InsulatedGateBi-PolarTransistors(IGBT)usedtoproducetheoutputpulsewidthmodulated(PWM) waveform,allowingforquietmotoroperation.

e.SelfdiagnosticswithfaultandpowercodeLEDindicator.FieldaccessoryDisplayKitavailableforfurther diagnosticsandspecialsetupapplications.

f.RS485capabilitystandard.

g.Electronicthermaloverloadprotection.

h.5%swingingchokesforharmonicreductionandimprovedpowerfactor.

i.Allprintedcircuitboardsshallbeconformalcoated.

3.IntegratedEconoMi$er®IV,EconoMi$er2,andEconoMi$erXstandardleakratemodels,factoryorfield-installed.

a.Integrated,geardrivenopposingmodulatingbladedesigntypecapableofsimultaneouseconomizerand compressoroperation.

b.Independentmodulesforverticalorhorizontalreturnconfigurationshallbeavailable.Verticalreturnmodulesshallbeavailableasafactory-installedoption.

c.Damperbladesshallbegalvanizedsteelwithcompositegears.Plasticorcompositebladesonintakeorre- turnshallnotbeacceptable.

d.Shallincludeallhardwareandcontrolstoprovidefreecoolingwithoutdoorairwhentemperatureand/or humidityarebelowsetpoints.

e.Shallbeequippedwithgeardrivendampersforboththeoutdoorventilationairandthereturnairforpositiveairstreamcontrol.

f.Standardleakratemodelsshallbeequippedwithdampersnottoexceed2%leakageat1in.wgpressure differential.

g.EconomizercontrolleronEconoMi$erIVmodelsshallbeHoneywellW7212thatprovides:

(1.)CombinedminimumandDCVmaximumdamperpositionpotentiometerswithcompressorstagingrelay. (2.)Functionswithsolidstateanalogenthalpyordrybulbchangeovercontrolsensing.

(3.)ContainLEDindicatesfor:whenfreecoolingisavailable,whenmoduleisinDCVmode,whenexhaustfancontactisclosed.

h.EconomizercontrolleronEconoMi$erXmodelsshallbetheHoneywellW7220thatprovides: (1.)2-lineLCDinterfacescreenforsetup,configurationandtroubleshooting.

(2.)On-boardFaultDetectionandDiagnostics(FDD)thatsensesandalertswhentheeconomizerisnot operatingproperly,perCaliforniaTitle24.

(3.)Sensorfailurelossofcommunicationidentification. (4.)Automaticsensordetection.

(5.)Capabilitiesforusewithmultiple-speedindoorfansystems.

(6.)Utilizedigitalsensors:DrybulbandEnthalpy.

i.EconomizercontrolleronEconoMi$er2modelswithPremierLink™controllershallbe4-20mAdesignand controlledbythePremierLinkcontroller.ThePremierLinkcontrollerdoesnotcomplywithCaliforniaTitle 24FaultDetectionandDiagnostic(FDD)requirements.

j.EconomizercontrolleronEconoMi$er2modelswithRTUOpencontrollershallbea4-20mAdesigncon- trolleddirectlybytheRTUOpencontroller.RTUOpencontrollermeetsCaliforniaTitle24FaultDetection andDiagnostic(FDD)requirements.

k.Shallbecapableofintroducingupto100%outdoorair.

l.Shallbeequippedwithabarometricreliefdampercapableofrelievingupto100%returnairandcontain sealsthatmeetASHRAE90.1-2016andIECC-2015requirements.

m.Shallbedesignedtoclosedamper(s)duringloss-of-powersituationswithspringreturnbuiltintomotor.

n.Drybulboutdoorairtemperaturesensorshallbeprovidedasstandard.Enthalpysensorisalsoavailablefor factory-installedeconomizersonly.Outdoorairsensorsetpointshallbeadjustableandshallrangefrom40 to100°F(4to38°C).Additionalsensoroptionsshallbeavailableasaccessories.

o.Theeconomizercontrollershallalsoprovidecontrolofanaccessorypowerexhaustunitfunction.Factory setat100%,witharangeof0%to100%.

p.Theeconomizershallmaintainminimumairflowintothebuildingduringoccupiedperiodandprovidede- signventilationrateforfulloccupancy.

q.Dampersshallbecompletelyclosedwhentheunitisintheunoccupiedmode.

r.Economizercontrollershallaccepta2-10VdcCO2sensorinputforIAQ/DCVcontrol.Inthismode, dampersshallmodulatetheoutdoorairdampertoprovideventilationbasedonthesensorinput.

s.CompressorlockouttemperatureonW7220isadjustablefrom-45°Fto80°F,setatafactorydefaultof 32°F.Othersshallopenat35°F(2°C)andcloseat50°F(10°C).

t.Actuatorshallbedirectcoupledtoeconomizergear.Nolinkagearmsorcontrolrodsshallbeacceptable.

u.Economizercontrollershallprovideindicationswheninfreecoolingmode,intheDCVmode,ortheex- haustfancontactisclosed.

4.IntegratedEconoMi$er®2,andEconoMi$erXUltraLowLeakratemodels,factoryorfield-installed.

a.Integrated,geardrivenopposingmodulatingbladedesigntypecapableofsimultaneouseconomizerand compressoroperation.

b.Independentmodulesforverticalorhorizontalreturnconfigurationshallbeavailable.Verticalreturnmod- ulesshallbeavailableasafactory-installedoption.

c.Damperbladesshallbegalvanizedsteelwithcompositegears.Plasticorcompositebladesonintakeorre- turnshallnotbeacceptable.

d.Shallincludeallhardwareandcontrolstoprovidefreecoolingwithoutdoorairwhentemperatureand/or humidityarebelowsetpoints.

e.Shallbeequippedwithgeardrivendampersforboththeoutdoorventilationairandthereturnairforposi- tiveairstreamcontrol.

f.UltraLowLeakdesignmeetsCaliforniaTitle24section140.4andASHRAE90.1-2016andIECC-2015 requirementsfor4cfmpersq.ft.ontheoutsideairdampersand10cfmpersq.ft.onthereturndampers.

g.EconomizercontrolleronEconoMi$erXmodelsshallbetheHoneywellW7220thatprovides: (1.)2-lineLCDinterfacescreenforsetup,configurationandtroubleshooting.

(2.)On-boardFaultDetectionandDiagnostics(FDD)thatsensesandalertswhentheeconomizerisnot

operatingproperly,perCaliforniaTitle24.

(3.)Sensorfailurelossofcommunicationidentification. (4.)Automaticsensordetection.

(5.)Capabilitiesforusewithmultiple-speedindoorfansystems.

(6.)Utilizedigitalsensors:DrybulbandEnthalpy.

h.EconomizercontrolleronEconoMi$er2modelswithRTUOpencontrollershallbea4-20mAdesigncon- trolleddirectlybytheRTUOpencontroller.RTUOpencontrollermeetsCaliforniaTitle24FaultDetection andDiagnostic(FDD)requirements.

i.Shallbecapableofintroducingupto100%outdoorair.

j.Shallbeequippedwithabarometricreliefdampercapableofrelievingupto100%returnairandcontain sealsthatmeetASHRAE90.1-2016andIECC-2015requirements.

k.Shallbedesignedtoclosedamper(s)duringloss-of-powersituationswithspringreturnbuiltintomotor.

l.Drybulboutdoorairtemperaturesensorshallbeprovidedasstandard.Enthalpysensorisalsoavailablefor factory-installedeconomizersonly.Outdoorairsensorsetpointshallbeadjustableandshallrangefrom40 to100°F(4to38°C).Additionalsensoroptionsshallbeavailableasaccessories.

m.Theeconomizercontrollershallalsoprovidecontrolofanaccessorypowerexhaustunitfunction.Factory setat100%,witharangeof0%to100%.

n.Theeconomizershallmaintainminimumairflowintothebuildingduringoccupiedperiodandprovidede- signventilationrateforfulloccupancy.

o.Dampersshallbecompletelyclosedwhentheunitisintheunoccupiedmode.

p.Economizercontrollershallaccepta2-10VdcCO2sensorinputforIAQ/DCVcontrol.Inthismode, dampersshallmodulatetheoutdoorairdampertoprovideventilationbasedonthesensorinput.

q.CompressorlockouttemperatureonW7220isadjustablefrom-45°Fto80°F,setatafactorydefaultof 32°F.Othersshallopenat35°F(2°C)andclosesat50°F(10°C).

r.Actuatorshallbedirectcoupledtoeconomizergear.Nolinkagearmsorcontrolrodsshallbeacceptable.

s.Economizercontrollershallprovideindicationswheninfreecoolingmode,intheDCVmode,ortheex- haustfancontactisclosed.

5.Two-PositionDamper(factory-installed)

a.DampershallbeaTwo-PositionDamper.Dampertravelshallbefromthefullclosedpositiontothefield adjustable%-opensetpoint.

b.Dampershallincludeadjustabledampertravelfrom25%to100%(fullopen).

c.Dampershallincludesingleordualblade,geardrivendampersandactuatormotor.

d.Actuatorshallbedirectcoupledtodampergear.Nolinkagearmsorcontrolrodsshallbeacceptable.

e.Damperwilladmitupto100%outdoorairforapplicablerooftopunits.

f.Dampershallcloseuponindoor(evaporator)fanshutoffand/orlossofpower.

g.Thedamperactuatorshallplugintotherooftopunit’swiringharnessplug.Nohardwiringshallberequired.

h.Outsideairhoodshallincludealuminumwaterentrainmentfilter

i.NotavailablewithStagedAirVolume(SAV™)models.

6.HeadPressureControlPackage(Motormaster®)

a.Controllershallcontrolcoilheadpressurebycondenserfanspeedmodulationorcondenserfancyclingand windbaffles.

b.Shallconsistofsolidstatecontrolandcondensercoiltemperaturesensortomaintaincondensingtemperature between90°F(32°C)and110°F(43°C)atoutdoorambienttemperaturesdownto-20°F(-29°C).

7.CondenserCoilHailGuardAssembly

a.Shallprotectagainstdamagefromhail.

b.Shallbelouvereddesign.

8.Unit-Mounted,Non-FusedDisconnectSwitch:

a.Switchshallbefactory-installed,internallymounted.

b.NationalElectricCode(NEC)andULapprovednon-fusedswitchshallprovideunitpowershutoff.

c.Shallbeaccessiblefromoutsidetheunit.

d.Shallprovidelocalshutdownandlockoutcapability.

e.Sizedonlyfortheunitasorderedfromthefactory.Doesnotaccommodatefield-installeddevices.

9.ConvenienceOutlet:

a.Poweredconvenienceoutlet.

(1.)Outletshallbepoweredfrommainlinepowertotherooftopunit.

(2.)Outletshallbepoweredfromlinesideorloadsideofdisconnectbyinstallingcontractor,asrequiredbycode.Ifoutletispoweredfromloadsideofdisconnect,unitelectricalratingsshallbeETLcertified andratedforadditionaloutletamperage.

(3.)Outletshallbefactory-installedandinternallymountedwitheasilyaccessible115-vfemale receptacle.

(4.)Outletshallinclude15ampGFIreceptacleswithindependentfuseprotection.

(5.)Voltagerequiredtooperateconvenienceoutletshallbeprovidedbyafactory-installedstepdown transformer.

(6.)Outletshallbeaccessiblefromoutsidetheunit.

(7.)Outletshallincludeafield-installed“WetinUse”cover.

b.Factory-InstalledNon-Poweredconvenienceoutlet.

(1.)Outletshallbepoweredfromaseparate115-120vpowersource. (2.)Atransformershallnotbeincluded.

(3.)Outletshallbefactory-installedandinternallymountedwitheasilyaccessible115-vfemalereceptacle.

(4.)Outletshallinclude15ampGFIreceptacles. (5.)Outletshallbeaccessiblefromoutsidetheunit.

(6.)Outletshallincludeafield-installed“WetinUse”cover.

c.Field-InstalledNon-Poweredconvenienceoutlet.

(1.)Outletshallbepoweredfromaseparate115-120vpowersource.

(2.)Atransformershallnotbeincluded.

(3.)Outletshallbefield-installedandinternallymountedwitheasilyaccessible115-vfemalereceptacle. (4.)Outletshallinclude20ampGFIreceptacles.Thiskitprovidesaflexibleinstallationmethodwhich

allowscodecomplianceforheightrequirementsoftheGFCIoutletfromthefinishedroofsurfaceas

wellasthecapabilitytorelocatetheoutlettoamoreconvenientlocation. (5.)Outletshallbeaccessiblefromoutsidetheunit.

(6.)Outletshallincludeafield-installed“WetinUse”cover.

10.Thru-the-BaseConnectors:

a.Kitsshallprovideconnectorstopermitelectricalconnectionstobebroughttotheunitthroughtheunitbasepan.

b.Minimumofthreeconnectionlocationsperunit.

11.PropellerPowerExhaust:

a.Powerexhaustshallbeusedinconjunctionwithanintegratedeconomizer.

b.Independentmodulesforverticalorhorizontalreturnconfigurationsshallbeavailable.

c.Horizontalpowerexhaustshallbemountedinreturnductwork.

d.Powerexhaustshallbecontrolledbyeconomizercontrolleroperation.Exhaustfansshallbeenergizedwhen dampersopenpastthe0-100%adjustablesetpointontheeconomizercontrol.

12.RoofCurbs(Vertical):

a.Fullperimeterroofcurbwithexhaustcapabilityprovidingseparateairstreamsforenergyrecoveryfromthe exhaustairwithoutsupplyaircontamination.

b.Formedgalvanizedsteelwithwoodnailerstripandshallbecapableofsupportingentireunitweight.

c.Permitsinstallationandsecuringofductworktocurbpriortomountingunitonthecurb.

13.HighStaticIndoorFanMotor(s)andDrive(s):

a.Highstaticmotor(s)anddrive(s)shallbefactory-installedtoprovideadditionalperformancerange.

14.Thru-the-BottomUtilityConnectors:

a.Kitshallprovideconnectorstopermitgasandelectricalconnectionstobebroughttotheunitthroughthe basepan.

15.OutdoorAirEnthalpySensor:

a.Theoutdoorairenthalpysensorshallbeusedtoprovidesingleenthalpycontrol.Whenusedinconjunction withareturnairenthalpysensor,theunitwillprovidedifferentialenthalpycontrol.Thesensorallowsthe unittodetermineifoutsideairissuitableforfreecooling.

16.ReturnAirEnthalpySensor:

a.Thereturnairenthalpysensorshallbeusedinconjunctionwithanoutdoorairenthalpysensortoprovide differentialenthalpycontrol.

17.IndoorAirQuality(CO2)Sensor:

a.Shallbeabletoprovidedemandventilationindoorairquality(IAQ)control.

b.TheIAQsensorshallbeavailableinductmount,wallmount,orwallmountwithLEDdisplay.Theset- pointshallhaveadjustmentcapability.

18.Smokedetectors(Factory-InstalledOnly):

a.ShallbeaFour-WireControllerandDetector.

b.Shallbeenvironmentalcompensatedwithdifferentialsensingforreliable,stable,anddrift-freesensitivity.

c.Shallusemagnetactivatedtest/resetsensorswitches.

d.Shallhavetool-lessconnectionterminalaccess.

e.Shallhavearecessedmomentaryswitchfortestingandresettingthedetector.

f.Controllershallinclude:

(1.)Onesetofnormallyopenalarminitiationcontactsforconnectiontoaninitiatingdevicecircuitona firealarmcontrolpanel.

(2.)TwoForm-Cauxiliaryalarmrelaysforinterfacewithrooftopunitorotherequipment.

(3.)OneForm-Csupervision(trouble)relaytocontroltheoperationoftheTroubleLEDonaremotetest/ resetstation.

(4.)Capableofdirectconnectiontotwoindividualdetectormodules.

(5.)Canbewiredtoupto14otherductsmokedetectorsformultiplefanshutdownapplications.

19.Horn/StrobeAnnunciator

a.Providesanaudible/visualsignalingdeviceforusewithfactory-installedoptionorfield-installedaccessory smokedetectors.

(1.)Requiresinstallationofafield-supplied24-vtransformersuitablefor4.2VA(AC)or3.0VA(DC)per horn/strobeaccessory.

(2.)Requiresfield-suppliedelectricalbox,NorthAmerican1-gangbox,2-in(51mm)x4-in(102mm). (3.)Shallhaveaclearcoloredlens.

20.WinterStartkit

a.Shallcontainabypassdevicearoundthelow-pressureswitch.

b.Shallberequiredwhenmechanicalcoolingisrequireddownto25°F (-4°C).

c.Shallnotberequiredtooperateonaneconomizerwhenbelowanoutdoorambientof40°F(4°C).

21.TimeGuard

a.Shallpreventcompressorshortcyclingbyprovidinga5-minutedelay(2minutes)beforerestartingacom- pressoraftershutdownforanyreason.

b.Onedeviceshallberequiredpercompressor.

22.ElectricHeat:

a.HeatingSection

(1.)Heaterelementopencoilresistancewire,nickel-chromealloy,0.29inchesinsidediameter,strungthrough ceramicinsulatorsmountedonmetalframe.Coilendsarestakedandweldedtoterminalscrewslots.

(2.)Heaterassembliesareprovidedwithintegralfusingforprotectionofinternalheatercircuitsnot exceeding48ampseach.Autoresetthermolimitcontrols,magneticheatercontactors(24Vcoil)and terminalblockallmountedinelectricheatercontrolbox(minimum18gagalvanizedsteel)attachedto endofheaterassembly.

23.HingedAccessPanels

a.Shallprovideeasyaccessthroughintegratedquarterturnlatches.

b.Shallbeonmajorpanelsof:filters,controlbox,fanmotorandcompressor.

24.DisplayKitforVariableFrequencyDrive

a.KitallowstheabilitytoaccesstheVFDcontrollerprogramstoprovidespecialsetupcapabilitiesanddiagnostics.

b.Kitcontainsdisplaymoduleandcommunicationcable.

c.DisplayKitcanbepermanentlyinstalledintheunitor used onanySAV™systemVFDcontrollerasneeded.

25.CondensateOverflowSwitch

a.Thissensorandrelatedcontrollermonitorsthecondensatelevelinthedrainpanandshutsdown compressionoperationwhenoverflowconditionsoccur.Itincludes:

(1.)Indicatorlight-solidred(morethan10secondsonwatercontact-compressorsdisabled),blinking red(sensordisconnected).

(2.)10seconddelaytobreak-eliminatesnuisancetripsfromsplashingorwavesinpan(sensorneeds10 secondsofconstantwatercontactbeforetripping).

(3.)Disablesthecompressor(s)operationwhencondensateplugisdetected,butstillallowsfanstorunfor Economizer.

26.ManualDamper

a.ManualDamperpackageshallconsistofdamper,airinletscreen,andrainhoodwhichcanbepresettoadmitupto25or50%outdoorairforyear-roundventilation.NotavailablewithStagedAirVolume(SAV™) models.

27.SupplyDuctCover:(14sizeonly.)

a.Requiredwhenfieldconvertingthefactorystandardverticalductsupplytohorizontalductsupplyconfiguration.Onerequiredperunit.

28.DisconnectSwitchBracket(14sizeonly)

a.Providesapre-engineeredandsizedmountingbracketforapplicationsrequiringaunitmountedfusedand non-fuseddisconnectofgreaterthan100amps.Bracketassuresthatnodamagewilloccurtocoilswhen mountingwithscrewsandotherfasteners.