Technical Specification

1.  Refrigeration Service Equipment for HFC-134a Refrigerant - VACUUM PUMP

Minimum Required Technical Specification / Technical Specification Proposed by Bidder
Brand Name:
Model:
General Requirements
The equipment is warranty for at least 1 year after date of commissioning;
The equipment will be supplied with a Thai-Language instruction manual and an English-Language instruction manual;
The suppliers must deliver and provide hand-on training on operation and maintenance of equipment on site at each vocational college.
Technical Specification
Two-stages vacuum pump;
Free air displacement not less than 4 CFM;
Motor power minimum 1/3 HP;
Micron Rating 25 microns or better at factory test;
Electrical supply 220 VAC, 50 Hz, Single Phase;
Check valve prevents oil back-flow during power failure;
Intake fittings or vacuum port to comply with SAE standard or equivalent for HFC-134a refrigerant;
Built in oil level sight glass to check the proper level of oil in the housing;
ON/OFF switch at the pump;
Certified to the recognized safety and technical standard in this field such as CE, UL, SAE, or equivalent. Name of the standard must be provided.

2. Refrigeration Service Equipment for HFC-134a Refrigerant – PRESSURE GAUGE

Minimum Required Technical Specification / Technical Specification Proposed by Bidder
Brand Name:
Model:
General Requirements
The equipment is warranty for at least 1 year after date of commissioning;
The equipment will be supplied with a Thai-Language instruction manual and an English-Language instruction manual;
The suppliers must deliver and provide hand-on training on operation and maintenance of equipment on site at each vocational college.
Technical Specification
Gauge manifold set is equipped with two color-coded valves operation;
One compound gauge (0-30 in. Hg. Vacuum, 0-120 PSI) and one pressure gauge(0-500 PSI) calibrated for HFC-134a;
Dial face of gauges show temperature and pressure. The unit of measurement must be indicated;
One set of three color-coded hoses, with at least 500 PSI working pressure & 2,500 PSI burst pressure. The standard hose shall have hose length of at least 72 inches;
The standard hoses are equipped with 1/4” SAE ports connection. The coupler for connecting to HFC-134a MAC system must be provided;
Certified to the recognized safety and technical standard in this field such as CE, UL, SAE, or equivalent. Name of the standard must be provided.

3. Refrigeration Service Equipment for HFC-134a Refrigerant – LEAK DETECTOR

Minimum Required Technical Specification / Technical Specification Proposed by Bidder
Brand Name:
Model:
General Requirements
The equipment is warranty for at least 1 year after date of commissioning;
The equipment will be supplied with a Thai-Language instruction manual and an English-Language instruction manual;
The suppliers must deliver and provide hand-on training on operation and maintenance of equipment on site at each vocational college.
1 set of leak detector comprises of electronic type and UV detection type. The supplier can propose leak detector that could perform dual detection (electronic detection and UV detection) in one unit;
Technical Specification of Electronic Type
Perform electronic leak detection;
Cordless and Portable;
Built-in sensitivity adjustment mode;
Equipped with flexible probe;
Audible alarm and visual indicator to be a detectable signal;
Detect leakage of CFC, HCFC, and HFC refrigerant;
Power source: Batteries (DC);
Certified to the recognized safety and technical standard in this field such as CE, UL, SAE, or equivalent. Name of the standard must be provided.
Technical Specification of UV Detection Type
Cordless and Portable;
Equipped with a UV lamp, an injection gun, a UV enhancing safety glasses, and a hose that connects supplied UV dye cartridge to 1/4” SAE ports connection including coupler for connecting to HFC-134a MAC system;
Power source for UV lamp: Batteries (DC). The batteries may be rechargeable type. If the rechargeable battery type is proposed, a battery charger must be supplied;
Supplied with 5 sets of at least 4 oz. of universal dye cartridges (compatible to supplied UV lamp) or in any other cartridge size with equivalent quantity;
Supplied with at least 4 oz. of dye cleaner;
Certified to the recognized safety and technical standard in this field such as CE, UL, SAE, or equivalent. Name of the standard must be provided.

4. Refrigeration Service Equipment for HFC-134a Refrigerant – ELECTRONIC CHARGING SCALE

Minimum Required Technical Specification / Technical Specification Proposed by Bidder
Brand Name:
Model:
General Requirements
The equipment is warranty for at least 1 year after date of commissioning;
The equipment will be supplied with a Thai-Language instruction manual and an English-Language instruction manual;
The suppliers must deliver and provide hand-on training on operation and maintenance of equipment on site at each vocational college.
Technical Specification
Charging of refrigerant by weight and weight resolution is at least 10 gram;
Weight capacity of at least 70 kilograms;
Equipped with LCD display to monitor the amount of refrigerant charged;
Read in kilogram or lb ;
Automatically stop when the amount of refrigerant charged into system reach the programmed amount (programmable);
Supplied with hose equipped with 1/4” SAE ports connection;
Supplied in durable case;
Electrical supply
AC: 220 VAC, 50 Hz, Single Phase; or
DC: Feature an auto-off function and low battery indicator;
Certified to the recognized safety and technical standard in this field such as CE, UL, SAE, or equivalent. Name of the standard must be provided.

5. Portable Recovery & Recycling Machine

Definition

“Recovery” means To remove refrigerant in any conditions from the system and store it in an external container.

“Recycling” means The process of reducing contaminations in refrigerant recovered from the system by oil separation, non-condensable removal and core filter-driers which will result in reduction of moistures, acidities, and particular matter.

Minimum Required Technical Specification / Technical Specification Proposed by Bidder
Brand Name:
Model:
General Requirements
The machine is warranty for at least 1 year after date of commissioning;
The equipment will be supplied with a Thai-Language instruction manual and an English-Language instruction manual;
The suppliers must deliver and provide hand-on training on operation and maintenance of equipment on site at each vocational college

Technical Specification

The machine is portable and in robust housing in enclosed cabinet;
The machine is capable of handling CFC-12, HCFC-22, HFC-134a and R-410A refrigerant;
Oil-free compressor and at least 1/3 HP motor;
Minimum vapor recovery rate 0.35 lb/minute and minimum liquid recovery rate 2.60 lb/minute;
The machine has automatic high pressure cut-off switch and overfill sensor cord for overfill protection;
Built-in high and low pressure gauges;
Replaceable core filter assembly;
Self clearing to ensure that refrigerants are not mixed when applying to other units;
The machine operates on a 220 Volt, 50 Hz and single-phase power supply.
Certified to the recognized safety and technical standard in this field such as CE, UL, SAE, or equivalent. Name of the standard must be provided
Accessories
The portable recovery and recycling unit must be equipped with the followings:
Four 30 lb. DOT standard refrigerant recovery cylinder with liquid level switch (floating switch) for overfilling protection, including 2 valves for liquid and vapor
Four sets of core filter elements (additional to the one supplied with the unit);
One set of refrigerant service hoses with manual shut-off (ball valve), 60 inches long to support the recovery & recycling with the unit;
Two tube piercing pliers and two piercing valves;
Process tube adapter kit for adapting tubing to charging hose support for 3/8, 1/4, 5/16 inch copper tubing;
A set of dust cover.

6. Refrigerant Identifier

Definition

The refrigerant identifier is used to identify percent weight concentration of R-12, R-22, R-134a, hydrocarbon and air contained in inspected refrigerant.

Minimum Required Technical Specification / Technical Specification Proposed by Bidder
Brand Name:
Model:

General Requirements

One set of refrigerant identifier comprises of the followings:
Main Set
One refrigerant identifier;
Two sets of sample hoses (comprising of R-12 sample hose, R-134a sample hose, and R-134a tank adapter fitting);
One 12 VDC vehicle power cable;
One 12 VDC internal rechargeable battery and one battery charger for 220 VAC, 50 Hz, Single Phrase;
One AC power supply (AC adapter) - Input 220VAC 50 Hz, Single Phase, Output 12VDC;
One set of service adapter kits comprising of the followings:
·  1/4" MFL x 1/4" FFL (90๐ Adapter)
·  1/4" MFL x 3/16" FFL (90๐ Adapter)
·  1/4" MFL x 1/4" FFL (45๐ Adapter)
·  1/4" MFL x 3/16" FFL (45๐ Adapter)
·  1/4" MFL x 1/4" FFL (Flexible Adapter)
One durable portable carrying case for rugged protection for prevention damage occurred from general water splash;
Spare Part Set
Five sample filters in packaging that prevent deterioration of sample filters;
Three printer paper rolls
The equipment is warranty for at least 1 year after date of commissioning;
The equipment will be supplied with a Thai-Language instruction manual and an English-Language instruction manual;
The suppliers must deliver and provide hand-on training on operation and maintenance of equipment on site at each vocational college.

Technical Specification of Refrigerant Identifier

The refrigerant identifier is portable design;
The refrigerant identifier utilizes non-dispersive infrared (NDIR);
The refrigerant identifier shall determine and provide weight concentration of R-12, R-22, R-134a, hydrocarbon and air;
Resolution: The refrigerant identifier shall read percentage of weight concentration to one decimal point;
The refrigerant identifier is certified to SAE J1771 or equivalent;
The refrigerant identifier shall have alarm indication and light illumination to alert if hydrocarbon concentrations are sensed to be 2% or greater by weight;
Refrigerant sample size not greater than 14 grams per test;
Refrigerant identifier can be operated from supplied rechargeable battery, from supplied operated with 12 VDC vehicle power cable and from supplied AC power supply (AC adapter);
The refrigerant identifier is equipped with built-in printer for printing test result;
Others
The supplier must prepare refrigerant in order to perform commissioning of all refrigerant identifiers. Types of refrigerant that shall be available for commissioning include at least HFC-134a and HCFC-22. The supplier shall also be responsible for performing testing of equipment during the commissioning;

All equipment may be scaled in SI Unit which is equivalent to the numbers shown above. For instance, the temperature, the pressure gauge, the port connection may be scaled either in o F or o C, PSI or KPa, inch or m.m. respectively